Diagnostic Messages - Siemens ET 200SP Manual

Technology module tm pulse 2x24v
Hide thumbs Also See for ET 200SP:
Table of Contents

Advertisement

5.2

Diagnostic messages

Enabling of diagnostic interrupts
You enable the diagnostics interrupts in the device configuration.
The technology module can trigger the following diagnostics interrupts:
Table 5- 4
Possible diagnostic interrupts
Diagnostic interrupt
Parameter error
Channel/component temporarily unavailable
Internal error
Watchdog tripped. Module is defective.
Error at digital outputs
Error
Load voltage missing
Short-circuit / overload at external sensor supply
Supply voltage fault
Overtemperature
Reactions to a diagnostic interrupt
The following happens when an event occurs that triggers a diagnostic interrupt:
● The DIAG LED flashes red.
When you have eliminated all errors, the DIAG LED stops flashing red and turns green.
● The S7-1500 CPU interrupts the processing of the user program. The diagnostic interrupt
OB (e.g. OB 82) is called. The event that triggered the interrupt is entered in the start
information of the diagnostic interrupt OB.
● The S7-1500 CPU remains in RUN, even if no diagnostic interrupt OB is present in the
CPU. The technology module continues working unchanged if this is possible despite the
error.
You can obtain detailed information on the error event in the error organization block with
instruction "RALRM" (Read additional alarm information), in the information system of
STEP 7 and in function manual Diagnostics
(https://support.industry.siemens.com/cs/ww/en/view/59192926), section "System
diagnostics in user program".
If the module is being operated as a distributed module in an ET 200SP system with
PROFIBUS DP, you have the option of reading out diagnostic data with the RDREC or
RD_REC instruction using data record 0 and 1. You can find the structure of the data records
in the manual for the IM 155-6 DP HF interface module available for download on the
Internet (https://support.industry.siemens.com/cs/ww/en/view/73098660).
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
Monitoring
Monitoring is always active. A diagnostic interrupt is triggered
each time an error is detected.
Monitoring is always active. An error detected only triggers a
diagnostics interrupt if "Diagnostics DQA" or "Diagnostics DQB"
has been enabled in the device configuration.
Monitoring is always active. An error detected only triggers a
diagnostics interrupt if "Group diagnostics" has been enabled in
the device configuration.
Interrupts/diagnostic messages
5.2 Diagnostic messages
145