Siemens ET 200SP Manual page 122

Technology module tm pulse 2x24v
Hide thumbs Also See for ET 200SP:
Table of Contents

Advertisement

Feedback bit/value
Explanations
ERR_LD
This bit indicates that the value in SLOT or LD_SLOT (when MODE_SLOT = 0) is invalid and was
not accepted.
The bit is reset once you have acknowledged the error with RES_ERROR.
ERR_24V
This bit indicates a short-circuit or an overload at output 24VDC If you have enabled diagnostic
interrupts, the diagnostic interrupt "Short circuit / overload of the sensor supply voltage" is triggered
when this error occurs.
The bit is reset once you have acknowledged the error with RES_ERROR.
ERR_PWR
This bit indicates that supply voltage L+ is too low. If you have enabled the diagnostic interrupts,
the diagnostic interrupt "Supply voltage fault" is triggered when an error occurs.
As soon as supply voltage L+ is sufficiently high again, ERR_PWR is automatically reset.
The bit is not set if no supply voltage is present.
STS_SW_ENABLE
This bit indicates the status of the SW enable.
STS_READY
This bit indicates that the module is supplying valid user data. The module is started and config-
ured.
STS_LD_SLOT
A status change (toggling) of this bit indicates that the LD_SLOT load request was detected and
executed (when MODE_SLOT = 0).
STS_DI
This bit indicates the status of the digital input DIn.0.
STS_DQA
This bit indicates the status of the digital output DQn.A.
STS_DQB
This bit indicates the status of the digital output DQn.B.
STS_ENABLE
This bit indicates that an output sequence is active.
Reserved
Reserved bits are set to 0.
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
0 means: SW enable not active
1 means: SW enable active
Configuring/address space
4.6 PWM with DC motor motor
121