5. Handling Component
Equipment
Modules
MELSfC GOT
Switch setbing
Contents
Name
3
Loop test (auxiliary loop)
4
Loop test (main loop)
This mode checks the circuits between two stations.
Inter-station test mode (main station)
5
This mode checks the circuits after all of the stations
have been connected. It
sets aH
of the stations other
than those being chxked in the on-line mode and
then runs the test (only with optical loop systems).
The
station with the lower number serves as the main
6
station, and the
as the sub &tion,
Inter-station test mode (sub station)
This
checks the hardware, including sending and
reception circuits and
cables
in the transmission
system, based on the network unit as a stand-alone
module.
This checks the hardware, including sending and
the network module as a stand-alone module.
7
Self-test
8
reception circuits in the transmission system, based on
Internal self-test
9
Hardware
test
I
This
checks
hardware
inside
the
network
module.
D
Station no. check
F
Group no. check
E
Network no. check
This checks the network number, group number, and
station numbers specified for the network module.
Let's
look
at how the self-test is carried out.
The self-test checks the hardware of the network module, including sending and recep-
tion circuits (main loops and auxiliary loops) and cables in the transmission system, based
on the network module as a stand-alone module.
For other testing methods, please refer to the MELSECNET/lO Network System Refer-
ence Manual (For PC Networks).
The self-test procedure is described below.
r
link con-
I
I
for self-test
1
Reverse side
@ Tum off the power supply to the GOT, and connect the optical
cable between the connectors of the network module, in a
folded-back connection.
For instructions on connecting a coaxial cable, please refer to
the MELSECNET/lO Network System Reference Manual (For
PC Networks).
@ Set the mode change setting switch on the network module to
"7" (this is the self-test setting).

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

A870got

Table of Contents