2 .
System Configuration
MELSEC GOT
(2) About the CQMl initialization
When using the RS232 port of the CQM1, write the values for the devices indicated below.
Perform initialization for the RS232C port of the CQMl using a peripheral tool or DM monitor.
Rerer to the CQMl Instruction Manual for details.
Device name
DM6645
Value to write
Device name
Value to write
-
OOWH
DM6649
OOOOH
DM6648
OOWH
DM6647
0 3 0 4 ~
DM6646
0001
H
~~-
(3) About the connection cable
The recommended convertor that can be used when connecting the CQMl and the GOT,
along with the connector and wiring, are indicated below. (Max. cable length: 200 m (7.87
ft4
(a) Supported convertors
Model
Manufacturer
'
EL Enaineerina
EL-LINE-I1
I
KS-1OP
I
Svstem
Sacom.
Ltd.
I
(b) Wiring connections when using EL-LINE-I1
RS-232ClRS-422
convertor
I
I
CQMl
RS232
signals
RS422
signals
GOT
I
I
6 S G
I
? - - - - - I
2
-
23