Advertisement

5. Handling Component
Equipment
Modules
MELSEC GOT
5.4.2
Installing the
tws
c o r r d o n
module
This shows how to install a bus connection module in the GOT. For more detailed information on
installing a bus connection module and entering the settings, please refer to the A7GT-BUS/
A7GT-BUS 2 User's Manual.
0 Before installing a bus connection module in the GOT, or removing a module already
I
@
DANGER
installed, switch all phases of the external power supply off to the GOT.
I
Reverse surface of GOT
Left side of bus
connection
module
Install the bus connection module to the GOT, then fix it in
place by tightening the screws of the bus connection module
within the range of specified torque, 39 to 59 N c m (4 to 6
kgcm).
To remove the bus connection module, loosen the screw, and
then reverse the installation procedure.
Connect the bus connection module and the main base/ex-
pansion base module using the expansion cable.
Set the expansion stage switch and I/O slot switch of the bus
connection module.
After setting these switches, turn on the power supplies
to the
PC CPU and the GOT.
This completes the procedure for entering settings for the bus
connection module.
Refer to Section 13.2 for instructions regarding the setting
method for the bus connection module's expansion stage
switch and I/O slot switch.