Spectrum Controls 1769 User Manual page 33

6-channel isolated rtd/resistance input module
Hide thumbs Also See for 1769:
Table of Contents

Advertisement

Data Format
Input
Engineering Units × 10
Type
˚ Celsius
-200 to
Pt 385
+850
-200 to
Pt 3916
+630
-100 to
10 Cu 426
+260
-100 to
100 Ni 618
+260
-80 to
120 Ni 672
+260
604 NiFe
-100 to
518
+200
150Ω
0 to +1500
500Ω
0 to +5004
1000Ω
0 to +10004
3000Ω
0 to +30004
NOTE
When resistances are selected, the temperature setting is ignored and the input data is the same for
4
either °C or °F selection.
Chapter 3: Module, Data, Status, and Channel Configuration
Raw/Proportional Data
Engineering Units × 1
Engineering Units × 10
Scaled for PID
Percent Range
Table 3-3. Channel Data Word Format
Engineering Units × 1
˚ Fahrenheit ˚ Celsius
-328 to
-2000 to
1562
+8500
-328 to
-2000 to
1166
+6300
-1000 to
-148 to 500
+2600
-1000 to
-148 to 500
+2600
-800 to
-112 to 500
+2600
-1000 to
-148 to 392
+2000
4
0 to +150004
0 to +50004
0 to +100004
0 to +300004
The engineering unit data formats represent real engineering temperature
units provided by the module to the controller. The raw/proportional
counts, scaled-for-PID and percent of full-scale data formats may yield the
highest effective resolutions, but may also require that you convert
channel data to real engineering units in your control program.
Raw/Proportional Data
The value presented to the controller is proportional to the selected input and
scaled into the maximum data range allowed by the bit resolution of the A/D
converter and filter selected. The raw/proportional data format also provides the
best resolution of all the data formats.
Scaled
For
˚ Fahrenheit
PID
-3280 to
0 to
15620
16383
-3280 to
0 to
11660
16383
-1480 to
0 to
5000
16383
-1480 to
0 to
5000
16383
-1120 to
0 to
5000
16383
-1480 to
0 to
3920
16383
0 to
16383
0 to
16383
0 to
16383
0 to
16383
User's Manual Pub. 0300241-02 Rev. A
Proportional
Percentage
Counts
-32767 to
0 to 10000
32767
-32767 to
0 to 10000
32767
-32767 to
0 to 10000
32767
-32767 to
0 to 10000
32727
-32767 to
0 to 10000
32767
-32767 to
0 to 10000
32767
-32767 to
0 to 10000
32767
-32767 to
0 to 10000
32767
-32767 to
0 to 10000
32767
-32767 to
0 to 10000
32767
3-5