Automatic start/Monitored start operation modes

Operation modes (è Fig. 11):
The Automatic start" (automatic reset) operation mode is preset with a
current bridge from terminal 5 to terminal 6 in the multi−pin plug socket
(on delivery).
The Monitored start" (monitored reset) operation mode should be seen as a
subordinate start from the perspective of the entire system. The enable signal
from the safety relay or the control system always has priority.
Note
The impulse generated by the start button has to be within a time−frame of 0.1 s
and 2 s.
If the start button is held down for two long or locked down, the system ident
ifies a cross fault and the device is placed in fault mode.
Automatic start
(condition upon delivery)
Fig. 11
Festo MS6−SV 0706NH English
Monitored start
41