Automatic Test Report; Dual Ip - Bosch AMAX panel 2100 Installation Manual

Hide thumbs Also See for AMAX panel 2100:
Table of Contents

Advertisement

AMAX panel
When on-board output 1 or 2 fails, the report will be sent. When the on-board output resumes
to normal conditions, the programmable output fault recovery report will be sent.
Communication Path 1 - 4 Fault
When any communication path fails, the report will be sent. When communication resumes to
normal conditions, the communication fault recovery report will be sent.
Changing Programming Parameters
When the programming parameters are changed and take effect, the report will be sent.
Keypad Emergency Alarm Reporting
If you press and hold both 1 and 3 for 3 seconds, or press and hold both [#] and [*] for 3
seconds, the emergency alarm report will be sent.
The emergency alarm report has no corresponding alarm recovery report.
Keypad Fire Alarm Reporting
If you press and hold both 4 and 6 for 3 seconds, the fire alarm report will be sent.
The fire alarm report has no corresponding alarm recovery report.
Keypad Medical Aid Reporting
If you press and hold both 7 and 9 for 3 seconds, the medical aid alarm report will be sent.
The medical aid alarm report has no corresponding alarm recovery report.
Automatic Test Reporting
The system supports sending automatic test report.
For more information about test report time programming, refer to Reports Programming, page
113.
Report Expiry Time
If the report expiry time expires and the report path has not been connected to, the report will
be lost and not be sent. It can be maintained for 1 to 255 minutes. The system is defaulted to
000, indicating that the report has been tried to send without limit in expiry time.
Report Delay Entry Time
This option defines the delay time until a report is send or a domestic calling is initiated when
an alarm occurs during entry time. The possible value range is 00-99 seconds. If 00 is selected
and an alarm occurs during entry time, a report is send immediately or the domestic calling is
initiated immediately after the entry time ends. The default setting is 30.
6.1.3

Automatic Test Report

There are two types of automatic test reports, periodic and regular daily reports.
Periodic automatic test reports are sent every hour specified in the test report interval. If 0 is
selected, the periodic test report is disabled.
Regular daily automatic test reports are sent at the same time every day. This option is only
possible if the date and time of the system is set correctly.
6.1.4

Dual IP

Dual IP Settings are valid only when used with Conettix IP communication format. IP module 1
is ITS-DX4020-G module or B426 module; IP module 2 is B426 module. IP module 2 does not
support RPC connection.
Bosch Sicherheitssysteme GmbH
All manuals and user guides at all-guides.com
Installation Manual
Settings | en
45
2015.05 | 06 | F.01U.309.277