ATTACK PELLET Series Instructions For Use Manual page 28

Voiler for combustion of wooden pellets

Advertisement

Tabel of settings
Pot.1
Blinking Fuel ignition
0x
30 sec
1x
45 sec
2x
60 sec
3x
75 sec
4x
90 sec
5x
105 sec
6x
120 sec
7x
135 sec
8x
150 sec
9x
165 sec
Factory settings
75 sec
Tabel applicable only for control boards marked by green point.
Burner settings
If the appliance does not work properly:
-
Check the level of pellets. The openings should be covered with pellets
during the operation mode.
-
In too high level of pellets, enhance the air inlet by opening the ventilator flap, or
(changing P2) reduce the pellet feeding.
-
Check the flue gas temperature (usually it moves between 120 and 170 °C). If
the temperature is too high: reduce the pellet feeding on P2. If the temperature is
too low: enhance the air inlet by ventilator flap.
-
In too low fuel level in burner check the flue gas temperature so, as described
above and close the air inlet, or enhance the pellet feeding. (P2).
-
Pellet feeding to be changed by P2 on control board (increase by clockwise
rotation, decrease by anticlockwise rotation). Check also the air inlet flap and the
flue gas temperature.
ALLERT: To keep the warranty and to reach the optimum combustion use the
flue gas analyzer in settings.
Pot.2
Feeding cycle
Burning out time
1,5 sec
1,65 sec
1,82 sec
2,18 sec
2,83 sec
3,68 sec
4,79 sec
6,22 sec
7,46 sec
8,21 sec
3,68 sec
8
Pot.3
Pot.4
Transitional interval Photocell
30 sec
45 sec
60 sec
90 sec
90 sec
135 sec
120 sec
180 sec
150 sec
225 sec
180 sec
270 sec
210 sec
315 sec
240 sec
360 sec
270 sec
405 sec
300 sec
450 sec
150 sec
270 sec
Pot.5
0
1
2
3
4
5
6
7
8
9
5

Advertisement

loading

This manual is also suitable for:

Pellet 20 aPellet 30 a