Quick Start
5-12 Terminal 27 Digital Input
5-14 Terminal 32 Digital Input
5-40 Function Relay
(Relay 1 Selection)
5-40 Function Relay
(Relay 2 Selection)
6-22 Terminal 54 Low Current
6-23 Terminal 54 High Current
6-29 Terminal 54 mode
6-70 Terminal 45 Mode
6-71 Terminal 45 Analog Output
6-90 Terminal 42 Mode
6-91 Terminal 42 Analog Output
7-20 Process CL Feedback 1 Resource
Table 3.2 Process Closed Loop
Application
Local/remote
Description
For applications where the speed reference can be switched
between local potentiometer and remote current signal
FC 360
+24V 12
DI1
18
Start
DI2
19
DI3
27
Coast inverse
DI4
29
DI5
32
Setup select
DI6
33
DI7
31
COM 20
+10V 50
AI1
53
4-20
54
AI2
mA
-
+
COM 55
45
AO1
AO2
42
1
R1
2
3
4
R2
5
6
Parameter settings
Set-up 1
0-10 Active Set-up
[9] Multi Set-up
0-12 Link Setups
[20] Linked
1-00 Configuration
[0] Speed Open
Mode
Loop
3-00 Reference Range
[0] Min–Max
3-15 Reference 1 Source [1] AI 53
3-16 Reference 2 Source
4-12 Motor Speed Low
25.0 Hz
Limit [Hz]
MG06A502
Quick Guide
[2] Coast Inverse
[14] Jog
[5] Running
[9] Alarm
4.0 mA
20.0 mA
[0] Current Mode
[0] 0–20 mA
[100] Output frequency
[0] 0–20 mA
[103] Motor Current
[2] Analog input 54
Set-up 2
[9] Multi Set-up
[20] Linked
[0] Speed Open
Loop
[0] Min–Max
[2] AI 54
25.0 Hz
Danfoss A/S © Rev. 06/2014 All rights reserved.
4-14 Motor Speed High
50.0 Hz
Limit [Hz]
5-10 (DI 18
[8] Start
Selection)0-10 Active
Set-up
5-10 Terminal 18 Digital
[2] Coast Inverse
Input
5-14 Terminal 32 Digital
[23] Set-up select
Input
5-40 Function Relay
[5] Running
(Relay 1 Selection)
5-40 Function Relay
[9] Alarm
(Relay 2 Selection)
6-10 Terminal 53 Low
0.07 V
Voltage
6-11 Terminal 53 High
10 V
Voltage
6-19 Terminal 53 mode [1] Voltage Mode
6-22 Terminal 54 Low
Current
6-23 Terminal 54 High
Current
6-29 Terminal 54 mode
6-70 Terminal 45 Mode [0] 0–20 mA
6-71 Terminal 45
[100] Output
Analog Output
frequency
6-90 Terminal 42 Mode [0] 0–20 mA
6-91 Terminal 42
[103] Motor Current [103] Motor Current
Analog Output
Table 3.3 Local/Remote
50.0 Hz
[8] Start
[2] Coast Inverse
3
[23] Set-up select
[5] Running
[9] Alarm
4.0 mA
20.0 mA
[0] Current Mode
[0] 0–20 mA
[100] Output
frequency
[0] 0–20 mA
11
3