Quick Start
3.2 Hand On/Auto On Mode
After installation (see chapter 4 Installation), there are 2
simple ways to start up the frequency converter: Hand On
and Auto On mode. At the first power-up, it is in Auto On
mode.
3
3
On
Warn
Hand
D
Illustration 3.3 Location of Hand On, Off/Reset and Auto On
Keys on the NLCP
•
Press [Hand On] to provide a local start command
to the frequency converter. Press [
increase and decrease speed.
•
Press [Off/Reset] to stop the frequency converter.
•
Press [Auto On] to control the frequency
converter either via control terminals or serial
communication.
CAUTION
Since the frequency converter is in Auto On mode at first
power-up, the frequency converter may start the motor
directly.
NOTICE
5-12 Terminal 27 Digital Input has coast inverse as default
setting. Connect terminals 12 and 27 to test Hand On/
Auto On running.
For LCP operation, see chapter 5 Local Control Panel and
Programming.
10
OK
Alarm
Auto
Reset
On
Danfoss A/S © Rev. 06/2014 All rights reserved.
Quick Guide
3.3 Application Selections
Use the selections for quick application set-up of the most
common applications by setting 0-16 Application Selection.
When necessary, the selections can be modified for
individual needs. All selections are for Auto On mode.
NOTICE
When an application is selected, relevant parameters are
automatically set. Customer specific configuration of all
parameters based on specific requirements is still
possible.
CAUTION
On
If any of the applications below are selected, relay 1 is
set to [Running] and relay 2 is set to [Alarm]
Application
Pumps, fans, compressors
Description
For applications where a value (e.g. pressure, temperature) must
▲
▼
] and [
] to
be kept at a desired level by sensor feedback
FC 360
+24V 12
DI1 18
DI2 19
DI3 27
DI4 29
DI5 32
DI6 33
DI7 31
COM 20
+10V 50
AI1
53
AI2
54
COM 55
AO1 45
AO2 42
1
R1
2
3
4
R2
5
6
Parameter settings
Parameter
1-00 Configuration Mode
1-03 Torque Characteristics
3-00 Reference Range
3-15 Reference 1 Source
4-12 Motor Speed Low Limit [Hz]
4-14 Motor Speed High Limit [Hz]
5-10 Terminal 18 Digital Input
Start
Coast inverse
Jog
-
+
4-20
mA
Option/value
[3] Process Closed Loop
[1] Variable Torque
[0] Min- Max
[0] No Function
30.0 Hz
50.0 Hz
[8] Start
MG06A502