Warning And Alarm Code List - Danfoss VLT AutomationDrive FC 360 Quick Manual

Hide thumbs Also See for VLT AutomationDrive FC 360:
Table of Contents

Advertisement

Diagnostics and Troubleshoo...

7.3 Warning and Alarm Code List

An (X) marked in Table 7.1 means that action occurs. A warning precedes an alarm.
No.
Description
2
Live zero error
3
No motor
4
Mains phase loss
1)
7
1)
DC over voltage
8
1)
DC under voltage
9
Inverter overloaded
10
Motor ETR over temperature
Motor thermistor over
11
temperature
12
Torque limit
13
Overcurrent
14
Ground fault
16
Short circuit
17
Control word timeout
25
Brake resistor short-circuited
26
Brake overload
Brake IGBT/Brake chopper short-
27
circuited
28
Brake check
30
U phase loss
31
V phase loss
32
W phase loss
34
Fieldbus fault
35
Option fault
36
Mains failure
38
Internal fault
40
Overload T27
41
Overload T29
46
Gate drive voltage fault
47
24 V supply low
AMA check U
and I
51
nom
nom
52
AMA low I
nom
53
AMA big motor
MG06A502
Quick Guide
Warning
Alarm
Trip lock
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Danfoss A/S © Rev. 06/2014 All rights reserved.
Cause
Signal on terminal 53 or 54 is less than 50% of value set
in 6-10 Terminal 53 Low Voltage, 6-12 Terminal 53 Low
Current, 6-20 Terminal 54 Low Voltage and 6-22 Terminal
54 Low Current.
No motor has been connected to the output of the
frequency converter.
Missing phase on supply side, or too high voltage
imbalance. Check supply voltage.
Intermediate circuit voltage exceeds limit.
Intermediate circuit voltage drops below "voltage
warning low" limit.
More than 100% load for too long.
Motor is too hot due to more than 100% load for too
long.
Thermistor or thermistor connection is disconnected.
Torque exceeds value set in either 4-16 Torque Limit
Motor Mode or 4-17 Torque Limit Generator Mode.
Inverter peak current limit is exceeded.
Discharge from output phases to ground.
Short-circuit in motor or on motor terminals.
No communication to frequency converter.
Brake resistor is short-circuited, thus brake function is
disconnected.
The power transmitted to the brake resistor over the last
120 s. exceeds the limit. Possible corrections: Decrease
brake energy via lower speed or longer ramp time.
Brake transistor is short-circuited, thus brake function is
disconnected.
Brake resistor is not connected/working.
Motor phase U is missing. Check the phase.
Motor phase V is missing. Check the phase.
Motor phase W is missing. Check the phase.
Profibus communication issues have occurred.
Field bus or option B detects internal errors.
This warning/alarm is only active if the supply voltage to
the frequency converter is lost and 14-10 Mains Failure is
NOT set to [0] No Function.
Contact the local Danfoss supplier.
Check the load connected to terminal 27 or remove
short-circuit connection.
Check the load connected to terminal 29 or remove
short-circuit connection.
24 V DC may be overloaded.
Wrong setting for motor voltage and/or motor current.
Motor current is too low. Check settings.
The motor is too big for the AMA to operate.
7
7
41

Advertisement

Table of Contents
loading

Table of Contents