Numerical Local Control Panel Lcp - Danfoss VLT AutomationDrive FC 360 Quick Manual

Hide thumbs Also See for VLT AutomationDrive FC 360:
Table of Contents

Advertisement

Installation
Para-
Default
Terminal
meter
setting
Serial communication
61
68 (+)
8-3*
69 (-)
8-3*
Relays
[0] No
01, 02, 03
5-40 [0]
operation
[0] No
04, 05, 06
5-40 [1]
operation
Table 4.2 Terminal Descriptions
Control terminal functions
Frequency converter functions are commanded by
receiving control input signals.
Programme each terminal for the function it
supports in the parameters associated with that
terminal. See Table 4.2 for terminals and
associated parameters.
Confirm that the control terminal is programmed
for the correct function. See chapter 5 Local
Control Panel and Programming for details on
accessing parameters and programming.
The default terminal programming initiates
frequency converter functioning in a typical
operational mode.
MG06A502
Quick Guide
Using screened control cables
Description
The preferred method in most cases is to secure control
and serial communication cables with screening clamps
provided at both ends to ensure best possible high
Integrated RC-Filter for
frequency cable contact.
cable screen. ONLY for
If the ground potential between the frequency converter
connecting the screen
and the PLC is different, electric noise may occur that
when experiencing
disturbs the entire system. Solve this problem by fitting an
EMC problems.
equalising cable as close as possible to the control cable.
Minimum cable cross section: 16 mm
RS-485 interface. A
control card switch is
provided for
termination resistance.
Form C relay output.
Illustration 4.8 Screening Clamps at Both Ends
These relays are in
various locations
depending upon the
50/60 Hz ground loops
frequency converter
With very long control cables, ground loops may occur. To
configuration and size.
eliminate ground loops, connect one end of the screen-to-
Usable for AC or DC
ground with a 100 nF capacitor (keeping leads short).
voltage and resistive
or inductive loads.
RO2 in J1-J3 enclosure
is 2-pole, only
terminals 04 and 05
Illustration 4.9 Connection with a 100 nF Capacitor
are available
Avoid EMC noise on serial communication
This terminal is connected to ground via an internal RC
link. Use twisted-pair cables to reduce interference
between conductors. The recommended method is shown
in Illustration 4.10.
Illustration 4.10 Twisted-pair Cables
Danfoss A/S © Rev. 06/2014 All rights reserved.
PLC
PE
PE
PE
1
2
1
2
Minimum 16 mm
2
Equalising cable
PLC
PE
100nF
PE
FC
69
68
61
PE
PE
PE
1
2
1
2
Minimum 16 mm
2
Equalising cable
2
.
FC
<10 mm
PE
FC
<10 mm
FC
69
68
61
<10 mm
PE
21
4
4