7 Diagnostics and Troubleshooting

7.1 Warning and Alarm Types

Warning/
alarm type
Warning
Alarm
7
7
Trip
A trip is an action by the frequency converter to suspend
operation to prevent damages to the frequency converter
and other equipment. When a trip occurs, the motor
coasts to a stop. The frequency converter logic continues
to operate and monitor the frequency converter status.
After the fault condition is remedied, the frequency
converter is ready for a reset.
Trip Lock
A trip lock is an action by the frequency converter to
suspend operation to prevent damages to the frequency
converter and other equipment. When a trip lock occurs,
the motor coasts to a stop. The frequency converter logic
continues to operate and monitor the frequency converter
status. The frequency converter starts a trip lock only when
serious faults occur that can damage the frequency
converter or other equipments. After the faults are fixed,
the input power must be cycled before the reset of the
frequency converter.
40
Description
A warning indicates an abnormal operating
condition that may lead to an alarm. A warning
stops when the abnormal condition is removed.
An alarm indicates a fault that requires
immediate attention. It is always accompanied by
a trip or trip lock. The frequency converter must
be reset after an alarm.
Reset the frequency converter in any of 4 ways:
Press [Reset]
Digital reset input command
Serial communication reset input command
Auto reset
Danfoss A/S © Rev. 06/2014 All rights reserved.
Quick Guide

7.2 Warning and Alarm Displays

Setup 1
Illustration 7.1 Warning and Alarm Displays
An alarm or trip-lock alarm flashes in the display along
with the alarm number.
Setup 1
Illustration 7.2 Alarm/Trip Lock Alarm
In addition to the text and alarm code on the frequency
converter display, there are 3 status indicator lights. The
warning indicator light becomes yellow during an alarm.
The alarm indicator light becomes red and flashing during
an alarm.
Illustration 7.3 Status Indicator Lights
Status
Quick
Menu
Status
Quick
Menu
On
OK
Warn
Alarm
Hand
D
Reset
On
Main
Menu
Main
Menu
Auto
On
MG06A502