Object, Modification Analogue Inputs - Festo CPX-FB11 Manual

Cpx terminal
Hide thumbs Also See for CPX-FB11:
Table of Contents

Advertisement

A. Technical appendix
A.3.9 Object, modification analogue inputs
Attr.
Access
Data source
no.
100
Get/set
Force mode of the relevant channel
101
Get/set
Force state of the relevant channel
1)
Identical with the distribution of the data block of analogue input data. The value is congruent
with the value of the analogue input channel.
A−20
Object class:
111
Instances:
1 ... 32
The Force, Fail safe and Idle parameters for the analogue in
puts are administered in this object. The first analogue input
(channel 0) is administered in instance 1. The second ana
logue input (channel 1) in instance 2 etc.
The force mode for the analogue input of this instance is en
abled or blocked in attribute 100. This enable function is
switched after the system function which affects all channels
(placed in System object 114, attribute 121).
Information on the assignment can be found in section A.3.5
and section B.2.2.
Type
USINT
1)
INT
Festo P.BE−CPX−FB11−EN en 0306a
Function no.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents