2. Commissioning
2−36
Automatic parameterisation via the scanner
In order to force automatic parameterisation when a CPX
terminal is replaced or after Power On:
Make sure that the system parameter System start" of
·
the CPX terminal is set to System start with default para
meterisation and current CPX equipment status" (preset
ting).
Otherwise the parameters of the CPX terminal are write−pro
tected. Automatic parameterisation is not then possible.
Mark the appropriate CPX terminal in the register card
·
[ADR] under [Available Devices]. (ADR stands for auto
matic device replacement).
Select the setting [Configuration recovery] in the field
·
[ADR settings].
The scanner then automatically loads the set parameters into
the CPX terminal before it exchanges I/O data with the CPX
terminal.
Festo P.BE−CPX−FB11−EN en 0306a