A. Technical appendix
A.3.8 Object, modification analogue outputs
Attr.
Access
Description
no.
100
Get/set
Force mode of the relevant channel
101
Get/set
Force state of the relevant channel
102
Get/set
Fault mode of the relevant channel
103
Get/set
Fault state of the relevant channel
104
Get/set
Idle mode of the relevant channel
105
Get/set
Idle state of the relevant channel
1)
Identical with the distribution of the data block of the analogue output data. The value is congru
ent with the value of the analogue output channel.
Festo P.BE−CPX−FB11−EN en 0306a
Object class:
110
Instances:
1 ... 32
The Force, Fail safe and Idle parameters for the analogue out
puts are administered in this object. The first analogue out
put (channel 0) is administered in instance 1. The second
analogue output (channel 1) in instance 2 etc.
The relevant mode for the analogue output of this instance is
enabled or blocked in attributes 100, 102 and 104. This en
able function is subordinate to the system function which
affects all channels (placed in System object 114, attributes
121, 122 and 123).
Information on the assignment can be found in section A.3.5