Bus Termination With Terminating Resistors - Festo CPX-FB11 Manual

Cpx terminal
Hide thumbs Also See for CPX-FB11:
Table of Contents

Advertisement

1. Installation
1.4

Bus termination with terminating resistors

1
Resistor for bus
termination
(121
± 1 %,
0.25 W)
Fig. 1/8: Bus termination with resistor on the open style connection
1−28
Please note
Fit a bus termination to both ends of a bus segment. This
also applies when the bus module or bus interface is at the
beginning of a bus cable.
If the CPX terminal is at the end of the field bus system, a bus
termination will be required.
If you are using T−adapters, we recommend that you install
the terminating resistor at the unused output of the T−
adapter.
Recommendation:
Fit a resistor (121 , 0.25 W) for the bus termination between
the connections for CAN_L and CAN_H. Fig. 1/8 shows this as
an example with the open style connection.
1
2
3
4
5
Festo P.BE−CPX−FB11−EN en 0306a
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents