Chapter 4: Secured Series Front End Mode; Secured Series Front End Mode Description; Wiring The Secured Series Front End; Figure 17: Wiring The Prox.pad To The Secured Series Dcm - IEI Technology prox.pad Installation & Programming Manual

Proximity reader/keypad access control
Table of Contents

Advertisement

prox.pad Installation/Programming Manual

Chapter 4: Secured Series Front End Mode

Chapter 4 describes Secured Series Front End mode and supplies wiring diagrams and a programming chart specific to Secured Series
Front End mode.
4.1

Secured Series Front End Mode Description

In Secured Series Front End Mode, the prox.pad unit is used as a front end for an IEI Secured Series Door Control Module. The
prox.pad operates as "code only", "card only", "card or code" or "card and code" with the Secured Series Door Control Module.
Refer to the instruction manual with your Secured Series product for more information.
In Secured Series Front End Mode, the Secured Series Door Control Module makes all the access control decisions, controls the
locking device, controls the alarm output relays and the monitors REX and the door contacts.
The prox.pad maintains it's own set of programming commands for various keypad options.
4.2

Wiring the Secured Series Front End

You can connect the prox.pad as a front end to an IEI Secured Series Door Control Module by following the diagram below. Using
connector P3 on the prox.pad, connect the white wire to the Secured Series DCM's white/yellow wire or the the white/yellow terminal
strip and connect the green wire to the white/black wire or white/black terminal strip on the Secured Series DCM.
Use ALPHA 1295C (22AWG) 4-wire, stranded and shielded cable. The cable shield
drain wire must be grounded at the reader end to P1, pin 4 connection (DC Power
Page 70 of 86

Figure 17: Wiring the prox.pad to the Secured Series DCM

Supply Ground).
Document # 6055676, Rev 2.2, D4b