Cabling Overview - Huawei TaiShan 200 Series User Manual

Table of Contents

Advertisement

TaiShan 200 Server
User Guide (Model 2280)

5.8.1 Cabling Overview

Basic Guidelines
To ensure optimal heat dissipation, do not block the air exhaust vents of PSUs.
Common Methods
The methods of routing cables inside a cabinet are described as follows:
Issue 04 (2020-01-16)
NO TICE
Lay out and bind cables of different types (such as power and signal cables)
separately. Cables of the same type must be in the same direction. Route
cables near each other in crossover mode. Ensure that the distance between
power cables and signal cables is greater than or equal to 30 mm (1.18 in.)
when you lay out the cables in parallel.
If you cannot identify cables according to the cable labels, attach an
engineering label to each cable.
Protect cables from burrs, heat sinks, and active accessories, which may
damage the insulation layers of cables.
Ensure that the length of cable ties for binding cables is appropriate. Do not
connect two or more cable ties together for binding cables. After binding
cables properly, trim off the excess lengths of the cable ties and ensure that
the cuts are neat and smooth.
Ensure that cables are properly routed, supported, or fixed within the cable
troughs inside the cabinet to prevent loose connections and cable damage.
Coil any surplus lengths of cables and bind them to proper positions inside
the cabinet.
Route cables straightly and bind them neatly. The bending radius of a cable
varies depending on the position where the cable is bent.
If you need to bend a cable in its middle, the bending radius must be at
least twice the diameter of the cable.
If you need to bend a cable at the output terminal of a connector, the
bending radius must be at least five times the cable diameter, and the
cable must be bound before bending.
Do not use cable ties at a place where the cables are bent. Otherwise, the
cables may break.
Determine overhead cabling and underfloor cabling for power cables based
on specific conditions of the equipment room. Specifically, take into
consideration the AC power distribution frame (PDF), surge protector, and
terminal block.
Determine overhead cabling and underfloor cabling for service data cables
based on specific conditions of the equipment room.
Place the connectors of all service data cables at the bottom of the cabinet so
that the connectors are difficult to reach.
Copyright © Huawei Technologies Co., Ltd.
5 Install and Configure
56