Huawei TaiShan 200 Series User Manual page 43

Table of Contents

Advertisement

TaiShan 200 Server
User Guide (Model 2280)
Category
Altitude
Corrosive
gaseous
contaminant
Particle
contaminant
Acoustic
noise
Issue 04 (2020-01-16)
Specifications
3050 m (10000 ft.)
NOTE
ASHRAE 2015 compliant:
● ASHRAE Class A1 and A2 compliant: For altitudes above 900 m
(2952.72 ft.), the highest operating temperature decreases by 1°C
(1.8°F) for every increase of 300 m (984.24 ft.) in altitude.
● ASHRAE Class A3 compliant: For altitudes above 900 m (2952.72 ft.),
the highest operating temperature decreases by 1°C (1.8°F) for every
increase of 175 m (574.15 ft.) in altitude.
● ASHRAE Class A4 compliant: For altitudes above 900 m (2952.72 ft.),
the highest operating temperature decreases by 1°C (1.8°F) for every
increase of 125 m (410.10 ft.) in altitude.
Maximum corrosion product thickness growth rate:
● Copper corrosion rate test: 300 Å/month (meeting level G1
requirements of the ANSI/ISA-71.04-2013 standard on
gaseous corrosion)
● Silver corrosion rate test: 200 Å/month
● The equipment room environment meets the requirements of
ISO 14664-1 Class 8.
● There is no explosive, conductive, magnetic, or corrosive dust
in the equipment room.
NOTE
It is recommended that the particulate pollutants in the equipment room
be monitored by a professional organization.
The declared A-weighted sound power levels (LWAd) and
declared average bystander position A-weighted sound pressure
levels (LpAm) listed are measured at 23°C (73.4°F) in
accordance with ISO 7779 (ECMA 74) and declared in
accordance with ISO 9296 (ECMA 109).
● Idle:
– LWAd: 6.08 Bels
– LpAm: 45.2 dBA
● Operating:
– LWAd: 7.0 Bels
– LpAm: 53 dBA
NOTE
Actual sound levels generated during operation vary depending on server
configuration, load, and ambient temperature.
Copyright © Huawei Technologies Co., Ltd.
3 Product Specifications
36