Llvd Disconnected; Blvd Disconnected; Batt Loop Trip - Huawei Telecom Power TP48200A-DT19C2 User Manual

Hide thumbs Also See for Telecom Power TP48200A-DT19C2:
Table of Contents

Advertisement

TP48200A-DT19C1, TP48200A-DT19C2,
TP48200A-HT19C1 and TP48200A-HT19C2 Telecom
Power
User Manual
2.

4.2.7 LLVD Disconnected

Possible Causes
Measures
1.
2.
3.

4.2.8 BLVD Disconnected

Possible Causes
Measures
1.
2.
3.

4.2.9 Batt Loop Trip

Possible Causes
Measures
1.
2.
Issue 03 (2019-11-15)
Remove the SMU, reinstall it, and check whether the alarm is cleared. If the alarm still
exists, replace the SMU.
An AC power failure has occurred.
Loads are manually disconnected.
The load disconnection voltage has been set to a very high value on the SMU.
Check whether an AC power failure has occurred. If so, rectify the fault to restore the
AC power supply.
Check whether loads are manually disconnected. If so, check with other maintenance
personnel whether the loads can be reconnected.
Check whether the load disconnection voltage (44 V DC by default) has been set to a
very high value on the SMU. If so, adjust it to a normal value.
An AC power failure has occurred.
Batteries are manually disconnected.
The battery disconnection voltage has been set to a very high value on the SMU.
Check whether an AC power failure has occurred. If so, rectify the fault to restore the
AC power supply.
Check whether batteries are manually disconnected. If so, check with other maintenance
personnel whether the batteries can be reconnected.
Check whether the battery disconnection voltage (43 V DC by default) has been set to a
very high value on the SMU. If so, adjust it to a normal value.
The battery circuit breaker or fuse detection cable is loosely connected.
The battery circuit breaker has tripped or the battery fuse has blown.
The contactor is faulty.
Check whether the battery circuit breaker or fuse detection cable is loosely connected. If
so, reconnect the cable.
Check whether the battery circuit breaker has tripped or the battery fuse has blown. If so,
rectify the battery loop fault and then switch on the circuit breaker or replace the fuse.
Copyright © Huawei Technologies Co., Ltd.
4 Maintenance