TP48200A-DT19C1, TP48200A-DT19C2,
TP48200A-HT19C1 and TP48200A-HT19C2 Telecom
Power
User Manual
Pin
4
5
3
7
6
8

3.5 UIM02C

Panel
The user interface module (UIM02C) supports eight dry contact outputs, six dry contact
inputs, and seven sensor ports (including one ambient temperature and humidity input, one
water sensor input, two ambient temperature inputs, one door status sensor input, one smoke
sensor input, and one battery temperature input).
Figure 3-11 UIM02C panel
Ports
Table 3-7 UIM02C ports
Port Type
Sensor ports
Issue 03 (2019-11-15)
Signal
RX+
RX-
RX232
TX232
PGND
NA
Silk Screen
TEM-HUM
WATER
TEMP1
TEMP2
GATE
SMOKE
BTEMP
Copyright © Huawei Technologies Co., Ltd.
Description
Ambient temperature and humidity sensor
Water sensor
Ambient temperature sensor 1
Ambient temperature sensor 2
Door status sensor
Smoke sensor
Battery temperature sensor
3 Components
Description
Receives data over RS485.
Receives data over RS232.
Transmits data over RS232.
Connects to the ground.