1. Summary of components
Manifold sub-base with
additional supply for
electric outputs
Manifold sub-base
without supply
1-18
If sub-bases with additional supply are not required, the
manifold sub-base with the system supply can be fitted in any
desired position.
If manifold sub-bases with additional supply are required,
these must always be placed to the right of the system supply
(see also Fig. 1/8).
The additional load voltage for the electric outputs is sup-
plied via this manifold sub-base. The load voltage for the
output modules is also supplied via an M18 plug and can be
switched off separately. This manifold sub-base must always
be placed to the right of the system supply.
The use of a manifold sub-base with additional supply causes
the following (see also Fig. 1/8):
–
The load voltage for electric output modules will be
interrupted to the previous module on the left.
–
The load voltage supplied will be available to the inte-
grated module and, where applicable, to the following
modules on the right.
–
The operating and load voltage supplies for the valves
will be transmitted further.
–
Several additional supplies for electric outputs in a
CPX terminal are possible.
This sub-base serves for the electrical linking of modules
which do not require a separate load supply.
Festo P.BE-CPX-SYS-EN en 0112NH