1. Summary of components
Manifold sub-base with
additional supply for
electric outputs
Manifold sub-base
without supply
1-18
If sub-bases with additional supply are not required, the
manifold sub-base with the system supply can be fitted in any
desired position.
If manifold sub-bases with additional supply are required,
these must always be placed to the right of the system supply
(see also Fig. 1/8).
The additional load voltage for the electric outputs is sup-
plied via this manifold sub-base. The load voltage for the
output modules is also supplied via an M18 plug and can be
switched off separately. This manifold sub-base must always
be placed to the right of the system supply.
The use of a manifold sub-base with additional supply causes
the following (see also Fig. 1/8):
The load voltage for electric output modules will be
interrupted to the previous module on the left.
The load voltage supplied will be available to the inte-
grated module and, where applicable, to the following
modules on the right.
The operating and load voltage supplies for the valves
will be transmitted further.
Several additional supplies for electric outputs in a
CPX terminal are possible.
This sub-base serves for the electrical linking of modules
which do not require a separate load supply.
Festo P.BE-CPX-SYS-EN en 0112NH