Festo CPX Series Electronic Manual page 180

Hide thumbs Also See for CPX Series:
Table of Contents

Advertisement

C. General information
System parameters
Settings
Fail safe
Reset outputs
(pre-setting)
Hold last state
Accept fault mode
value
Table C/1: System parameter "Fail safe"
Module parameters Settings
Fault mode
Hold last state
Fault state
(pre-setting)
Fault state
Reset output
– Digital signal
(pre-setting)
Set output
– Analogue signal
Analogue value
Table C/2: Module parameters "Fault mode" and "Fault state"
C-10
Description
Reset all outputs/valves
Retain current signal status for all outputs/
valves
Accept the signal status defined for the relevant
channel
If "Accept fault mode value" is activated, the signal states
defined by module parameter for the relevant channel will
become effective (see Fig. C/4).
Description
Retain current signal status
Accept the signal status defined by fault state
Reset output signal (output/valve)
Set output signal (output/valve)
Value of the analogue signal
Method of operation
The "Fault mode" parameter is used to determine whether
the current signal status is to be retained or whether the sig-
nal status defined by "Fault state" is to be accepted.
Festo P.BE-CPX-SYS-EN en 0112NH

Advertisement

Table of Contents
loading

Table of Contents