Festo CPX Series Electronic Manual page 103

Hide thumbs Also See for CPX Series:
Table of Contents

Advertisement

5. Diagnosis and error treatment
Fault
Error
Operating status
number
class
0
-
No error
1
2
General diagnosis
(module-specific faults)
2
2
Short circuit/overload in sensor
supply (SCS) or output (SCO)
3
2
Reserved
4
2
Failure in load voltage supply due
to short circuit/overload (on output
side)
5
2
Undervoltage in the power supply
(on the input side)
6...8
2
Reserved
9
2
Reserved
10
2
Reserved
11
2
Short circuit at the valve
12
2
Reserved
13
2
Wire fracture (open load)
14
2
Reserved
15
2
Module/channel failure or incorrect
module
16
2
Module code not permitted
1) Power Off/On is required for quitting the fault depending on the parametrizing
Festo P.BE-CPX-SYS-EN en 0112NH
Error elimination
-
See manual for the relevant module
Eliminate short circuit/overload
-
Check connected actuators as well
as their connections
Eliminate undervoltage at system
supply or additional supply (pin 2)
-
-
-
Check valve and pneumatic interface
-
Check valve
-
Check module
Check CPX equipment status or save
CPX equipment status again (pro-
cedure see parameter System start;
function no. 4402)
1)
5-7