6-51 Terminal 42 Output Min Scale
Range:
*
0%
Motor current
Torque rel to lim
Torque rel to rated
Power
Speed
Torque

Ext. closed loop 1

Ext. closed loop 2
Ext. closed loop 3
Output freq. 4-20mA
Reference 4-20mA
Feedback 4-20mA
Motor cur. 4-20mA
Torque
%
lim.
4-20mA
Torque
%
nom
4-20mA
Power 4-20mA
Speed 4-20mA
Torque 4-20mA
Bus ctrl. 0-20 mA
Bus ctrl. 4-20 mA
Bus ctrl. 0-20 mA,
timeout
Bus ctrl. 4-20 mA,
timeout
Ext. Closed Loop 1,
4-20 mA
Ext. Closed Loop 2,
4-20 mA
Ext. Closed Loop 3,
Select the function of Terminal 42 as an analog current output.
4-20 mA
Function:
[0 – 200%]
Scale the minimum output of the selected analog signal at ter-
minal 42, as a percentage of the maximum signal value. E.g. if
0 mA (or 0 Hz) is desired at 25% of the maximum output value,
then programme 25%. Scaling values up to 100% can never be
higher than the corresponding setting in par. 6-52.
®
MG.20.P1.02 - VLT
is a registered Danfoss trademark
4. How to programme the frequency converter
4
89