4. How to programme the frequency converter
6-11 Terminal 53 High Voltage
Range:
10.0V
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
4
0.000
Unit
6-15 Terminal 53 High Ref./Feedb. Value
Range:
100.000
Unit
6-20 Terminal 54 Low Voltage
Range:
0.07V
6-21 Terminal 54 High Voltage
Range:
10.0V
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
0.000
Unit
6-25 Terminal 54 high ref./feedb. value
Range:
100.000
Unit
6-50 Terminal 42 Output
Option:
[0]
[100]
[101]
[102]
88
Function:
*
[Par. 6-10 to 10.0 V]
Enter the high voltage value. This analog input scaling value
should correspond to the high reference/feedback value set in
par. 6-15.
Function:
[-1000000.000 to par.
Enter the analog input scaling value that corresponds to the low
*
6-15]
voltage/low current set in par. 6-10 and 6-12.
Function:
[Par.
6-14
to
Enter the analog input scaling value that corresponds to the high
*
1000000.000]
voltage/high current value set in par. 6-11/6-13.
Function:
*
[0.00 – par. 6-21]
Enter the low voltage value. This analog input scaling value
should correspond to the low reference/feedback value, set in
par. 6-24.
Function:
*
[Par. 6-20 to 10.0 V]
Enter the high voltage value. This analog input scaling value
should correspond to the high reference/feedback value set in
par. 6-25.
Function:
[-1000000.000 to par.
Enter the analog input scaling value that corresponds to the low
*
6-25]
voltage/low current value set in par. 6-20/6-22.
Function:
[Par.
6-24
to
Enter the analog input scaling value that corresponds to the high
*
1000000.000]
voltage/high current value set in par. 6-21/6-23.
Function:
No operation
*
Output frequency
Reference
Feedback
MG.20.P1.02 - VLT