Danfoss VLT AQUA High Power Operating Instructions Manual page 133

Hide thumbs Also See for VLT AQUA High Power:
Table of Contents

Advertisement

VLT AQUA High Power Operation Instructions
Analog inputs:
Number of analog inputs
Terminal number
Modes
Mode select
Voltage mode
Voltage level
Input resistance, R
Max. voltage
Current mode
Current level
Input resistance, R
Max. current
Resolution for analog inputs
Accuracy of analog inputs
Bandwidth
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage
terminals.
Pulse inputs:
Programmable pulse inputs
Terminal number pulse
Max. frequency at terminal, 29, 33
Max. frequency at terminal, 29, 33
Min. frequency at terminal 29, 33
Voltage level
Maximum voltage on input
Input resistance, R
Pulse input accuracy (0.1 - 1 kHz)
Analog output:
Number of programmable analog outputs
Terminal number
Current range at analog output
Max. load to common at analog output
Accuracy on analog output
Resolution on analog output
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage
terminals.
i
i
i
®
MG.20.P1.02 - VLT
is a registered Danfoss trademark
5. General Specifications
Voltage or current
Switch S201 and switch S202
Switch S201/switch S202 = OFF (U)
: 0 to + 10 V (scaleable)
approx. 10 kΩ
Switch S201/switch S202 = ON (I)
0/4 to 20 mA (scaleable)
approx. 200 Ω
10 bit (+ sign)
Max. error 0.5% of full scale
: 200 Hz
110 kHz (Push-pull driven)
5 kHz (open collector)
see section on Digital input
28 V DC
approx. 4 kΩ
Max. error: 0.1% of full scale
0/4 - 20 mA
Max. error: 0.8 % of full scale
2
53, 54
± 20 V
30 mA
5
2
29, 33
4 Hz
1
42
500 Ω
8 bit
133