Danfoss VLT AQUA High Power Operating Instructions Manual page 34

Hide thumbs Also See for VLT AQUA High Power:
Table of Contents

Advertisement

3. How to Install
Kit Contents
3
All fasteners are either:
3.5.1. Installation of Rittal Enclosures
This illustration shows the full size template
included with the kit and two drawings that
may be used to locate the cutouts for the en-
closure top and bottom plates. The duct work
may also be used to locate the openings.
Install gasket material on the back openings
of the frequency converter prior to installation
on the enclosure back panel.
Use the template provided with the kit (shown
above) and install the frequency converter on
the back panel of the Rittal enclosure. The
template is referenced to the top-left corner
of the back panel. Therefore the template may
be used with any size back panel and both the
1800 mm and 2000 mm high enclosures.
34
Ductwork components
Mounting hardware
Gasket material
Delivered with D1 and D2 frame kits:
175R5639 - Mounting templates and top/bottom cut out for Rittal enclosure.
Delivered with E1 frame kits:
175R1036 - Mounting templates and top/bottom cut out for Rittal enclosure.
10 mm, M5 Nuts torque to 2.3 Nm (20 in-lbs)
T25 Torx screws torque to 2.3 Nm (20 in-lbs)
MG.20.P1.02 - VLT
VLT AQUA High Power Operation Instructions
Illustration 3.29: Templates
Illustration 3.30: Openings on rear not used in this
application
®
is a registered Danfoss trademark

Advertisement

Table of Contents
loading