VLT AQUA High Power Operation Instructions
0-01 Language
Option:
*
[0]
1-20 Motor Power [kW]
Range:
Size re-
lated
1-22 Motor Voltage
Range:
Size re-
lated
1-23 Motor Frequency
Range:
Size re-
lated
This parameter cannot be adjusted while the motor is running.
1-24 Motor Current
Range:
Size re-
lated
This parameter cannot be adjusted while the motor is running.
Function:
Defines the language to be used in the display.
English
Function:
[0.09 - 500 kW]
Enter the nominal motor power in kW according to the motor
*
nameplate data. The default value corresponds to the nominal
rated output of the unit.
This parameter cannot be adjusted while the motor is running.
Depending on the choices made in
tings
ble.
Function:
[10 - 1000 V]
Enter the nominal motor voltage according to the motor name-
*
plate data. The default value corresponds to the nominal rated
output of the unit.
This parameter cannot be adjusted while the motor is running.
Function:
[20 - 1000 Hz]
Select the motor frequency value from the motor nameplate
*
data. For 87 Hz operation with 230/400 V motors, set the name-
plate data for 230 V/50 Hz. Adapt par. 4-13
Limit [RPM)
application.
Function:
[0.1 - 10000 A]
Enter the nominal motor current value from the motor name-
*
plate data. This data is used for calculating motor torque, motor
thermal protection etc.
®
MG.20.P1.02 - VLT
is a registered Danfoss trademark
4. How to programme the frequency converter
par. 1-20 or par. 1-21 Motor Power
, either
Maximum Reference
and par. 3-03
par. 0-03 Regional Set-
is made invisi-
Motor Speed High
to the 87 Hz
4