Operational Check - Assa Abloy Sargent PASSPORT 1000 P1 Installation Instructions Manual

Mortise lock
Table of Contents

Advertisement

Passport 1000 P1 PoE Mortise Lock

Operational Check

8
IMPORTANT: Be sure to test functions prior to closing door.
In all cases, perform the following checks:
1. Ensure that inside lever retracts latch.
• For units with cylinders, the following checks apply:
Insert key into cylinder and rotate:
a. There should be no friction against lock case or any other
obstructions. If friction or binding occurs, re-adjust cylinder to
eliminate issues.
b. The key should retract the latch and the key should rotate freely.
c. The key should extend and retract the deadbolt.
• For units without a keypad, add card using LCT software* and test.
• For units with a keypad, add pin and card using LCT software* and test.
2. LED signaling:
• After using a valid credential, a green flash followed by three fast
amber flashes indicates a low power condition.
• Check the input voltage.
• If the input voltage is low, disconnect the lock from the power source
and check the power source voltage. If the power source voltage is
correct, inspect the lock wiring for a possible short.
If the lock loses power, it will flash rapid blue for approximately one
minute. Lock will default to programmed fail safe or fail secure.
After that, the lock will no longer be functional.
3. When you have completed the tests, close the door, ensuring latchbolt fully
extends into strike plate without binding.
*Refer to Network and Lock Configuration Tool user manual (WFMN1) for
information on how to configure and program locks.
1-800-810-WIRE • www.sargentlock.com • A8032G
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents