Configurations And Settings - Johnson Controls FMS-1655 Series Installation Manual

Room pressure controller
Hide thumbs Also See for FMS-1655 Series:
Table of Contents

Advertisement

MODULE SETTINGS
SUBHEAD
Configurations & Settings
Table 1. Analog Input Configuration Settings (S1)
Mode
S1 - 1
AI-1 5Vdc
OFF
AI-1 20mA
ON
AI-1 10Vdc
OFF
Not Valid
ON
AI-2 5Vdc
AI-2 20mA
AI-2 10Vdc
Not Valid
AI-3 5Vdc
AI-3 20mA
AI-3 10Vdc
Not Valid
AI-4 5Vdc
AI-4 20mA
AI-4 10Vdc
Not Valid
Table 2. Protocol Selection Settings (S3)
Protocol Selection
Reserved
Metasys® N2
BACnet® MS/TP (default)
Controller Configuration Dipswitch (S4)
1.
AO-1 Voltage Range Selection:
2.
AO-2 Voltage Range Selection:
3.
AO-3 Voltage Range Selection:
4.
AO-4 Voltage Range Selection:
Controller Configuration Slideswitch (S5):
LEFT = Digital Inputs pulled-high (triggered by active low input - default)
RIGHT = Digital Inputs pulled-low (triggered by active high input, up to 24Vdc)
S1 - 2
S1 - 3
S1 - 4
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
S3-7
OFF
ON
ON
OFF = 0-10Vdc
OFF = 0-10Vdc
OFF = 0-10Vdc
OFF = 0-10Vdc
-
45
-
S1 - 5
S1 - 6
S1 - 7
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
S3-8
OFF
OFF
ON
ON = 0 - 5Vdc
ON = 0 - 5Vdc
ON = 0 - 5 Vdc
ON = 0 - 5 Vdc
S1 - 8
OFF
OFF
ON
ON