4.2.3.3 Display object table
Object for setting the internal clock
Function:
Time signal
Object
Function
76
Time
h
Description
3-byte object for setting the internal clock. The time is required for indication
on the display or to control the heating timer (incl. day of the week) and the
valve protection. The weekday information is obtained from the KNX/EIB time
telegram.
Objects for display control
Function:
Value display
Object
Function
78
Value
h
Description
1-byte object for activation of the value display for display line 1.
This object is only available in this way if the display function is parameterised
for value display with a 1-byte display format (date).
Function:
Value display
Object
Function
78
Value
h
Description
2-byte object for activation of the value display for display line 1.
This object is only available in this way if the display function is parameterised
for value display with a 2-byte display format (date).
Function:
Value display
Object
Function
78
Value
h
Description
4-byte object for activation of the value display for display line 1.
This object is only available in this way if the display function is parameterised
for value display with a 4-byte display format (date).
1: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.
Order No. 5142 00
Order No. 5145 00
Software "Push button sensor 3 plus"
Name
Type
D.Input
3 byte
Name
Type
D.Input row 1
1 byte
Name
Type
D.Input row 1
2 byte
Name
Type
D.Input row 1
4 byte
Object table
DPT
Flag
10.001
C, W, -, (R)
1
DPT
Flag
5.0xx,
C, W, -, (R)
6.0xx
1
DPT
Flag
7.xxx,
C, W, -, (R)
8.xxx,
1
9.xxx
DPT
Flag
12.xxx,
C, W, -, (R)
13.xxx,
1
14.xxx
Page 74 of 281