Software "Push Button Sensor 3 Plus; Scope Of Functions - Gira 5142 00 Product Documentation

Push button sensor 3 plus 2-gang, push button sensor 3 plus 5-gang (2+3)
Table of Contents

Advertisement

4.2 Software "Push button sensor 3 plus"

4.2.1 Scope of functions

Functions of the integrated push button sensor
-
Each operating area can either be used as a single rocker or as two independent buttons.
-
For push button function either double-surface or single-surface principle.
-
Each rocker can be used for the functions 'switching', 'dimming', 'venetian bling', '1 byte
value transmitter', '2-byte value transmitter', 'scene extension','2-channel operation' and
'manual fan control'.
-
Each button can be used for the functions 'switching', 'dimming', 'venetian blind', '1 byte
value transmitter', '2 byte value transmitter', 'scene extension', '2-channel operation',
'controller extension', 'controller operation', 'heating timer operation' and 'manual fan
control'.
-
2-channel control is possible: each rocker or each button can be set for controlling two
independent channels. This means that only one button-press is enough to transmit up to
two telegrams to the bus. The channels can be configured independently of one another for
the Switching, Value transmitter (1 byte) or Temperature value transmitter (2 bytes)
functions.
-
For the rocker functions Dimming, Venetian blind (operation concept "Long – Short or
Short")' and 2-channel operation, full-surface rocker actuation can also be evaluated. With
full-surface rocker operation, switching telegrams and scene recall requests can be
triggered on the bus in addition to and independently of the configured rocker function.
-
The switching function permits the following settings: reaction after pressing and/or
releasing, switch on, switch off, and toggle.
-
The dimming function permits the following settings: times for short and long actuation,
dimming in different levels, telegram repetition on long press, transmission of stop telegram
after end of press.
-
The shutter control permits the following settings: four different operation concepts with
times for short and long press and slat adjustment.
-
The 1-byte and 2-byte value transmitter function permits the following settings: selection of
the value range (0 ... 100 %, 0 ... 255, 0 ... 65535, 0 ... 1500 lux, 0 ... 40 °C), value on
button-press, value change on sustained button-press with different step widths, optional
overflow on reaching the end of a value range.
-
The controller extension function or controller operation permits the following settings:
operating mode switch-over (defined selection of an operating mode or change between
different operating modes for a controller extension), change of presence status, setpoint
shift.
-
Each operating area has two status LEDs.
-
When a status LED is internally connected with the rocker or the button, it can signal a
button-press or the current status of a communication object. The status indication can also
be in inverted form.
-
When a status LED is not dependent on the rocker or button, it can be permanently on or
off, indicate the status of an independent communication object, the operating state of a
room temperature controller or the result of a comparison between signed or unsigned 1
byte values.
-
The colour of the status LEDs (red, green, blue) can be configured in the ETS either
globally or separately, as required. Optionally a superposed function can be activated via
the bus, in which the colour and display information of individual status LEDs can be
changed according to priority.
-
A delay to the automatically transmitted communication objects of the controller external
after a device reset can be configured. The delay time is automatically produced by the
subscriber address (physical address).
-
The rockers or buttons can be disabled via a 1-bit object. During an active disable, all or
some of the rockers / buttons can have no function, can perform the function of a selected
button or execute one of two presettable disabling functions.