10.3

Error on the interface

Error
No communication via
RS 232/RS 485
Sporadic errors on the
RS 232/RS 485 inter-
face
Leuze electronic
Possible error causes
• Incorrect wiring.
• Different baud rates.
• Different protocol
settings.
• Incorrect wiring.
• Effects due to EMC.
• Overall network expansion
exceeded.
BPS 8
Diagnostics and troubleshooting
Check wiring.
Check baud rate.
Check protocol settings.
Check wiring, in particular the shield of the
wiring.
Check the cable used.
Check shielding (shield covering in place up
to the clamping point).
Check grounding concept and connection to
FE.
Check max. network expansion as a func-
tion of the max. cable lengths.
Measures
114