CAUTION: Electrical connections MUST be made by specialised technicians.
-
Check that the power supply voltage indicated on the rear label (Fig. 5.3.1-1) corresponds to that
available at the point of installation.
-
The unit must be connected with an overload cut-out switch to a system fitted with an adequate earth
system that conforms to the standards applicable in the country of installation.
-
The system must be connected according to current standards.
-
Max variation in mains voltage: ±10%.
-
A differential switch with the following characteristics must be installed upstream the power socket of the
unit:
nominal current: 16 A.
differential sensitivity: 0.03 A.
-
Connect the supplied cable to the rear of the unit.
-
Position the unit so that the plug is accessible.
Do not allow the lead to bend tightly and do not place any object on it.
Do not use extension cords.
Only use the original lead.
ONLY USE ORIGINAL SPARE PARTS.
If the unit does not function correctly, please refer to Appendix 9 "Troubleshooting" of this manual for
possible causes. For further information or repairs, please contact your supplier or the technical department
of Euronda S.p.A.
WARNING. The unit conforms to the electrical safety requirements of the Standards Institute and comes
supplied with a double-pole plug that ensures the unit is earthed.
A fundamental safety requirement is to check that the electric system is appropriately connected to the
earth, and that the ratings of both system and sockets are suitable for the power of the unit, which is
shown on the rating plate (see chap. 5.3.1 "Rating plate"). Have the system checked by qualified
personnel.
EURONDA S.p.A DECLINES ALL LIABILITY IF THE ABOVE IS NOT OBSERVED.