Step
Connect PC serial port and Configuration Port of Profibus-DP master module
and apply the power of master module. Click Connect COM1 or other button
according to PC serial port and confirm if the corresponding module is
selected. As in the figure, Version and Date may have different value. If
there is no error, select the check box and click the OK button.
12
Configuration Download: Click Online > Download. It starts downloading,
all LED status is OFF and only READY LED blinks. After downloading, all
LED shows its function.
During the download, the following warning message appears.
After confirming if there is a problem in communication, click Yes to
download.
R210
Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide
November 2011
ATTENTION
When you click the Connect COM1 button, if the module information
does not appear normally and the error occurs, verify the connection
of cable for configuration and the cable condition.
Honeywell
6. Profibus-DP Communication
6.4. Tool for Communication Setting
Action
79