Honeywell 2MLL-PSRA User Manual

Pnet i/f module
Hide thumbs Also See for 2MLL-PSRA:
Table of Contents

Advertisement

Honeywell Process Solutions
Pnet I/F Module
2MLL-PSRA, 2MLL-PSEA
User's Guide
R210
November 2011
Release 210
Honeywell

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell 2MLL-PSRA

  • Page 1 Honeywell Process Solutions Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 November 2011 Release 210 Honeywell...
  • Page 2 In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
  • Page 3 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 References The following list identifies all documents that may be source of reference for material discussed in this publication. Document Title SoftMaster User’s Guide R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 4 Honeywell Global TAC – India Phone: +91-20- 6603-9400 Fascimile: +91-20- 6603-9800 Mail: Honeywell Automation India Ltd 56 and 57, Hadapsar Industrial Estate Hadapsar, Pune –411 013, India Email: Global-TAC-India@honeywell.com Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 5 GTAC-SEA@honeywell.com Taiwan Contact: Honeywell Global TAC – Taiwan Phone: +886-7-536-2567 Fascimile: +886-7-536-2039 Mail: Honeywell Taiwan Ltd. 17F-1, No. 260, Jhongshan 2nd Road. Cianjhen District Kaohsiung, Taiwan, ROC Email: Global-TAC-Taiwan@honeywell.com R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 6 20th Floor, 1-16-1 Kaigan, Minato-ku, Tokyo 105-0022, Japan Email: Global-TAC-JapanJA25@honeywell.com Elsewhere Call your nearest Honeywell office. World Wide Web Honeywell Solution Support Online: http://www.honeywell.com/ps Training Classes Honeywell Automation College: http://www.automationcollege.com Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 7 WARNING, Risk of electrical shock: Potential shock hazard where HAZARDOUS LIVE voltages greater than 30 Vrms, 42.4 Vpeak, or 60 VDC may be accessible. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 8 Chassis Ground: Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements. viii Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 9 Precautions in attaching the PLC ..................32 Wiring ......................34 Power wiring ......................... 34 I/O Device Wiring ......................... 35 Grounding Wiring ......................... 36 Cable specification for wiring....................37 SYSTEM CONFIGURATION ............39 Overview ......................39 R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 10 High-speed Link setting in SoftMaster-NM ..........80 How to set and download GSD ..............88 MAINTENANCE AND REPAIR ........... 89 I/O module maintenance ................89 Routine inspection ..................90 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 11 Action method when ERR LED is ON .................. 94 Action method when Program Write does not work ............. 95 SyCon connection error ....................... 96 SoftMaster-NM connection error ..................97 Communication error with slave ................... 97 R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 12: Table Of Contents

    Table 14 – Pnet High-speed Link setting contents ............50 Table 15 – Communication flag list ................52 Table 16 – Profibus-DP classification ................67 Table 17 – Operation sequence of High-speed Link............80 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 13 Figure 23 – I/O data refresh through I/O module and backplane bus ......72 Figure 24 – I/O data Communication through local USB ..........72 Figure 25 – Downloading configuration information through GSD file ......88 R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide xiii November 2011 Honeywell...
  • Page 14 Contents Figures Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 15 (analog current output)/RTD (Resistor temperature detector)/TC (Thermocouple) • Easy to configure the system. • Provides the online network status detection function. − Detects the remote module status through High-speed Link monitor. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 16: Figure 1 - Hot Swap Function

    Figure 1 – Hot swap function The characteristics of Pnet slave I/F module are as follows: • Supports open network by adopting a communication protocol of international standard. • Communicates with remote master module. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 17 Supports Global instructions. Synchronizes I/O data according to Sync, Unsync, Freeze, Unfreeze instruction. • Available to be used with diverse CPU modules. Available to be used with ML200/ML200R CPU modules. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 18: Table 1 - Product Configuration Of Digital I/O Module

    TR output 32 points (0.1A, source output) 2MLQ-TR8B TR output 64 points (0.1A, source output) 2MLQ-SS2A Triac output, 16 points (1A) Dustproof 2MLT-DMMA Dustproof module for unused slot module Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 19: Table 2 - Product Configuration Of Analog I/O Module

    RTD input 2MLF-RD4A RTD input, 4 channels module Product Configuration of the Pnet slave I/F module The following table provides the system configuration of the Pnet slave module. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 20 The maximum installation numbers are same as the number of High-speed link in use. When there are other communication modules using High-speed link, the number of all communication modules using High-speed link have to be less than 12. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 21: Table 3 - General Specifications Of Pnet I/F Module

    57 ≤ f ≤ 150Hz − 4.9m/s (0.5G) • Peak acceleration: 147 m/s (15G) Shock • Duration: 11ms IEC61131-2 resistance • Half-sine, 3 times each direction per each axis R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 22 Isolation performance of the devices. For instance, Pollution degree 2 indicates the state generally that only non- conductive pollution occurs. However, due to the dew produced, this state contains temporary conduction. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 23: Table 4 - Communication Specifications Of Pnet Remote I/F Module

    Communication speed and distance Speed (kbps) 1500 3000 6000 12000 Distance (m) Maximum node count 100 stations (setting range: 0 ~ 99 ) Maximum expansion module installation 12 modules count R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 24: Table 5 - Communication Specifications Of Pnet Slave I/F Module

    Interface RS-485 (electric) Media access Polling Topology Bus method Amplitude method Communication interface Auto baud rate Master/Slave Slave Maximum station count per network 99 stations (including master and repeater) Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 25 Main base ~ Expansion 3 2MLI-CPUH/S 2MLR-CPUH/ F, Main base 2MLR-CPUH/T Internal consumption current (mA) Weight (g) Profibus-DP cable specification Cable specification The following table lists the Profibus-DP cable specification. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 26: Table 6 - Profibus-Dp Cable Specification

    Output wire: green wire is connected to A2; red wire is connected to B2. • Shield is connected to connector’s clamp. • When installing the connector in terminal, connect the cable to A1 and B1. The following figure displays the connector’s structure. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 27: Figure 2 - Connector's Structure

    2.4. Profibus-DP cable specification Figure 2 – Connector’s structure The following figure displays the cable structure. Figure 3 – Cable structure The following figure displays the wire connection method. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 28: Figure 4 - Wire Connection Method

    2. Product Specifications 2.5. Pnet Terminating Figure 4 – Wire connection method Pnet Terminating The following figure displays Pnet termination. Figure 5 – Pnet termination Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 29 3. Installation and wiring Installation Installation environment The 2MLL-PSRA 2MLL-PSEA modules have high reliability regardless of their installation environment. The following factors ensure the system reliability and stability. − Environmental prerequisites Avoid installing the module in places where it is subjected or exposed to: Water leakage and dust.
  • Page 30 3.1. Installation Precautions during installation of Profibus-DP module Station number in the range of 0~99 is available for 2MLL-PSRA, and station number in the range of 0~98 is available for 2MLL-PSEA. The following precautions must be taken during the installation of the 2MLL-PSRA and 2MLL-PSEA modules.
  • Page 31: Figure 6 - Wiring The I/O Line

    In case the inductive load is connected to the output part, connect the surge killer or diode to the load in parallel. Connect the cathode of the diode to the ‘+’ side of the power. Figure 6 – Wiring the I/O line R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 32: Figure 7 - Installing Plc To Control Panel

    Figure 7 – Installing PLC to control panel − Use a different panel for large sized electronic contactor or the vibration source such as no-fuse breaker and install PLC separately. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 33: Figure 8 - Installing The Duct

    In case the equipment is installed in front of the PLC (inside the door) to avoid the effect of radiant noise or the heat, separate it from the PLC of distance more than 100mm. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 34: Figure 9 - Power Wiring

    For PLC, I/O machine and power machine, it is required to divide the power as follows. Where T1, T2: Constant voltage transformer. − Use 2mm² thick power cable to reduce the voltage fluctuation. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 35: Figure 10 - Surge Absorber

    While wiring, maintain a distance of 80mm between the I/O signal cable and the high-voltage, high-current main circuit cable. − To separate the main circuit cable and the power cable, you should use the shielded cable, and earth the PLC. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 36: Figure 11 - I/O Device Wiring

    For grounding, use the electric wire that is more than 2mm² of thickness. Place the grounding point near this PLC if possible and shorten the length of the grounding cable. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 37: Table 7 - Cable Specification For Wiring

    Tighten the terminal screw with 6~9 kgcm torque. • Use the fork type screw for the compressed terminal. The following figure is an example of the proper compressed terminal (fork type). R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 38 3. Installation and wiring 3.2. Wiring Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 39: Figure 13 - Wiring For Dc Input Module

    External connection machine is located between the DC power and the (+) terminal of DC input module terminal. − Hence, when the power is ON, the current flows from external connection machine to DC input module terminal. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 40: Figure 14 - Basic System Configuration For Pnet Remote I/F Module

    In case the open/close frequency is high or module is used to open/close the conductive load, use the transistor output module. Basic System Configuration The 2MLL-PSRA and 2MLL-PSEA communicates with master and controls expansion I/O module through Backplane Bus. The following figure illustrates the basic system configuration for Pnet remote I/F module.
  • Page 41: Figure 16 - Part Names And Functions Of Pnet Remote I/F Module

    The following figure illustrates the part names and functions of Pnet remote I/F module. Figure 16 – Part names and functions of Pnet remote I/F module The following figure illustrates the part names and functions of Pnet slave I/F module. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 42: Figure 17 - Part Names And Functions Of Pnet Slave I/F Module

    4. System Configuration 4.2. Part names and functions Figure 17 – Part names and functions of Pnet slave I/F module Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 43: Table 8 - Led Status Of Pnet Remote I/F Module

    O/S is not operating (O/S operation error by H/W error) Master configuration and slave parameter are identical and data communication is normal P-RUN Data communication between the master and R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 44 I/O parameter error: I/O parameter set by user is different with actual I/O configuration. − When different parameter is downloaded during communication, ERR LED is OFF. − When different parameter is downloaded during not communicating, ERR LED is ON. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 45: Table 10 - Product List

    2MLI -A21A AC220V, 8 point 2MLI -D21A DC24V, 8 point Input module 2MLI -D22A DC24V, 16 point, sink/source 2MLI -D22B DC24V, 16 point, sink 2MLI -D24A DC24V, 32 point, sink/source R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 46: Table 13 - Analog I/O Module List

    Voltage input: 8 channels 2MLF-AC8A Current input: 8 channels 2MLF-AD8A Voltage/current input: 8 channels Analog input Voltage/current input: 4 channels, Isolation 2MLF-AD4S between channels 2MLF-AD16A Voltage/current input: 16 channels Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 47 Thermocouple input, 4 channels, Isolation 2MLF-TC4S type Temp. conversion 2MLF-RD4A RTD input, 4 channels ATTENTION For more information on specification of analog I/O module, refer to respective product’s user manual. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 48: Figure 18 - Example For System Configuration

    4. System Configuration 4.3. Example for system configuration Example for system configuration Figure 18 – Example for system configuration Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 49: Figure 19 - High-Speed Link Process

    As it is possible to communicate with other stations by simple parameter setting, it is easy to use High-speed Link. The High-speed Link process of internal data enables periodic, simultaneous processing of huge data. Figure 19 – High-speed Link process R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 50: Table 14 - Pnet High-Speed Link Setting Contents

    Refer to ML200R User’s Guide for memory address. (Master module  Slave Indicate I/O point into Byte. Size module) (Byte) - Consider less than 8 bit I/O module as 1 Byte Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 51 When changing the CPU module, download backup parameter set in SoftMaster-NM and write it to the new CPU module. For more details on SyCon, refer to section Profibus-DP Communication. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 52: Table 15 - Communication Flag List

    ON. L000000 _HS1_RLINK speed Link No.1 are normal. All stations set in parameter are RUN mode and there is no Error. All data blocks set in parameter operate properly. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 53 It indicates whether Kth data block of OCK[k] Array Parameter No.1 Kth parameter is set or not. L00041F Block Note: In case of Pnet, Kth block indicates slave’s station number. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 54 ~15 in the L00010. (16~31, 3 2~47,48~63, 64~79, 80~95, 96~111, 112~127 in the L00011, L00012, L00013, L00014, L00015, L00016, L00017). So block no. 55’s mode information in the L000137. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 55 Action In the SoftMaster-NA, click File > New File. The New project dialog box appears. From the Adapter type list, select 2MLL-PSRA and click OK. After connecting USB cable to Profibus-DP remote module, turn on the power. Click Online > Connection Settings.
  • Page 56: Figure 20 - Error Log

    If I/O parameter is different from the actual system configuration in main base, Profibus- DP remote module indicates Module type mismatch error. At this time, STATUS LED is OFF. Figure 20 – Error log Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 57 After synchronization, the following message appears. If module mismatch error appears, verify whether ERR LED is off or not. Check whether all the modules are registered at project window. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 58 Digital I/O module parameter setting: If you double-click the digital I/O module, emergency output setting window appears for the output module, and input filter setting window appears for input module. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 59 Before downloading, save the project and write the parameter. After completing the parameter setting, click Online > Write Parameter to download parameter. After download is complete, the following message appears. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 60 Enter the NM Project name and select the other details as per requirement, and click OK. The NM project with the specified name appears in the Project Window. From the Project Window, click the Standard settings and select the base Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 61 The following are the basic values for the Communication Module Setting. • Data bit = 8 • Stop bit = 1 • Parity bit = NONE • Modem type = Null modem R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 62 Start the SyCon tool. The SyCon window appears. Click Insert > Slave or from the top left toolbar, select and then click master to insert slave. The Insert Slave dialog box appears. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 63 5.3. How to set Pnet slave I/F module parameter Step Action In the Available slaves list, select 2MLL-PSRA if you are using 2MLL-PSRA and then click Add. If there are several masters for the slave, select one master at a time from the Master list and confirm the Station address and Description.
  • Page 64 Sync instruction: This is used to synchronize the output data of the slave station. If slave station receives Sync instruction from the master, it keeps lastly received output data as current output data. Slave repeats this action whenever it gets Sync Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell...
  • Page 65 Though actual input data changes, it keeps the value of moment when it receives Freeze instruction as input data. And slave repeats this action whenever it gets Freeze instruction of the master. Master cancels Freeze state by sending UnFreeze instruction. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 66 5. Communication Programming 5.3. How to set Pnet slave I/F module parameter Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 67: Table 16 - Profibus-Dp Classification

    RS-485 (Electric) Topology Modulation method NRZ (Non Return to Zero) MAX (media access method) Local token ring Distance Transfer speed (bps) Communication distance and transfer 9.6k/19.2k/93.7k/187.5 speed 1,200 500k R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 68 Basic Performance Overview Profibus-DP Master module sets the following functions. Supports only High-speed Link communication. − Uses parameter setting in SoftMaster-NM and Configuration Tool (Honeywell provided tool: SyCon). − Sets only sending/receiving area from SoftMaster-NM High-speed Link parameter setting. −...
  • Page 69 Sending/receiving number per slave station is set as byte unit (set in SyCon). Communication begins through SoftMaster-NM High-speed Link enable set. Operation by High-speed Link If Master module is the product of Honeywell (2MLL-PMEA), it configures Profibus Network using SyCon. Download Profibus Network Configuration to master module.
  • Page 70: Figure 21 - Sequence Operation To Establish Communication

    6. Profibus-DP Communication 6.3. Basic Performance Figure 21 – Sequence operation to establish communication Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 71: Figure 22 - I/O Data Communication Through Backplane Bus

    Slave I/F module refreshes data in TRX buffer through CPU module’s I/O image area and CPU module refreshes data in I/O image area through I/O module and backplane bus. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 72: Figure 23 - I/O Data Refresh Through I/O Module And Backplane Bus

    Figure 23 – I/O data refresh through I/O module and backplane bus − For expansion I/O module, write parameter through local USB connection. Figure 24 – I/O data Communication through local USB Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 73 Tool for Communication Setting Communication setting by SyCon If using master module provided by Honeywell (2MLL-PMEA), configure Profibus network using SyCon and download the information to the corresponding master module. As Profibus Network Configuration Tool is different for each master module, and if you are using Honeywell master module (2MLL-PMEA), use only SyCon.
  • Page 74 6. Profibus-DP Communication 6.4. Tool for Communication Setting Step Action Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 75 Click Buffered, host controlled under Handshake of the process data. Click OK. Click Insert > Slave or select from top left toolbar and click master to insert slave. The Insert Slave dialog box appears. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 76 6.4. Tool for Communication Setting Step Action In the Available slaves list, select 2MLL-PSRA and click the Add button if you are using 2MLL-PSRA. If there are several masters, select one from the Master, confirm Station address, and Description, and click OK.
  • Page 77 The Bus Parameter dialog box appears. Optimize field contains standard and user definition setting. Speed setting (Baud rate) contains 9.6kbps ~12Mbps setting. Normally, Baud rate is set as 1.5Mbps and Optimize is set as standard. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 78 Driver to be provided by 2MLL-PMEA type master module is only RS-232C port. Thus, CIF TCP/IP Driver, CIF Device Driver is not available. Driver Selection of CIF Serial Driver: Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 79 LED status is OFF and only READY LED blinks. After downloading, all LED shows its function. During the download, the following warning message appears. After confirming if there is a problem in communication, click Yes to download. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 80: Table 17 - Operation Sequence Of High-Speed Link

    High- Parameters Write speed Link. Click Online > Enable Link to High-speed Link enable the applicable High-speed Enable Link. SyCon For 2MLL-PMEA, start SyCon. Execute dedicated Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 81 Online > SyCon Upload on the High-speed Link window. Double-click the cell on the High- High-speed Link speed Link window. Block Setting • For Send : specify Read area R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 82 On the SoftMaster window, click Tools > Network Manager. The SoftMaster-NM window appears. Click File > New File. The New NM Project dialog box appears. Type the NM Project Name and select the PLC series. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 83 Local/Remote connection setting Connection Local: Connection from PC to settings CPU. Connection steps Remote: Connection from PC to CPU through communication module. Timeout interval 1~9 seconds when Common communication failure R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 84 Click Online > Read IO Information to read the modules installed on the base. Select High-speed Link tab on the SoftMaster-NM. Select the communication module and double-click the High-speed Link. The Communication Module Settings dialog box appears. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 85 Data is latched or cleared when CPU error Output data CPU is on Error. setup in case of Data is latched or cleared when emergency CPU stop CPU is Stop. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 86 If identical station No. is set, communication may not be normal. Sending: Data transmission from master module to slave module. Mode *1 Receiving: Data transmission from slave module to master module. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 87 Click Online > Enable Link. The Link Enable(HS Link,P2P) dialog box appears. Select the applicable High-speed Link and click Write. If the High-speed Link is enabled, then High-speed LED is ON. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 88: Figure 25 - Downloading Configuration Information Through Gsd File

    Master establishes the communication with Pnet remote I/F module and verifies the information of expansion I/O modules based on the downloaded information. Figure 25 – Downloading configuration information through GSD file Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell...
  • Page 89 Voltage measure Adjust the power within the allowable between terminals. Power supply voltage variance range. DC 20.4 ~ 28.8V R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 90 Check whether the LED Expansion I/O module System is ON. information match. Configuration Module detached, invalid module Check whether the LED installed, Out of I/O is ON. data range, I/O parameter error. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 91 Move the key switch to STOP and turn it ON/OFF. • Restricting range. Identify the reason for the fault. − Is it from the PLC or external factor? − I/O module or others? − PLC program? R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 92 8. Troubleshooting 8.3. Troubleshooting methods Troubleshooting methods The following procedure describes the detection methods, description for error codes, and corrective measures. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 93 8. Troubleshooting 8.3. Troubleshooting methods Action method when RUN LED is OFF This section describes the sequence of steps to be taken, if the RUN LED is OFF. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 94 8. Troubleshooting 8.3. Troubleshooting methods Action method when ERR LED is ON This section describes the sequence of steps to be taken, if the ERR LED is ON. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 95 8. Troubleshooting 8.3. Troubleshooting methods Action method when Program Write does not work This section describes the sequence of steps to be taken, if the Program Write does not work. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 96 8. Troubleshooting 8.3. Troubleshooting methods SyCon connection error This section describes the sequence of steps to be taken, if the SyCon connection error occurs. Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 97 This section describes the sequence of steps to be taken, if the SoftMaster-NM connection error occurs. SM-NM Communication error with slave This section describes the sequence of steps to be taken, if the communication error occurs with slave. R210 Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide November 2011 Honeywell...
  • Page 98 8. Troubleshooting 8.3. Troubleshooting methods Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide R210 Honeywell November 2011...
  • Page 100 Honeywell Process Solutions 1860 W. Rose Garden Lane Phoenix, AZ 85027 USA...