PWR
MOD
(Module
Status)
NET
(Network
Status)
1-4
Ports 1-4 DI
EIP 1
EIP 2
13.2.2 MD 248i-12-8K/L4-2R2K
The MD 248i-12-8K/L4-2R2K (8-port IP20 DIN rail model) provides these LEDs.
Leuze electronic
MD 748i-11-42/L5-2222 LEDs
A lit green PWR LED indicates that the IO-Link Master is powered.
The MOD LED provides the following information:
•
Off = No errors or there is no PLC connection
•
Flashing red
One or more errors detected when NET is off
Fatal error when NET is also flashing
•
Steady red = Maintenance required or demanded
The NET LED provides the following information:
•
Off = No PLC connection
•
Steady green = PLC connection established
•
Flashing red = Fatal error when MOD is also flashing
This LED provides the following information about the IO-Link port.
•
Off: SIO mode - signal is low or disconnected.
•
Yellow: SIO mode - signal is high.
•
Flashing red: Hardware fault - make sure that configured IO-Link settings on the
port do not conflict with the device that is attached:
Automatic Upload and/or Download is enabled and it is not the same
device.
Device Validation Mode is enabled and it is not the correct device.
Data Validation Mode is enabled but there is an error.
•
Solid red - PDI of the attached IO-Link device is invalid.
•
Solid Green: An IO-Link device is connected and communicating.
•
Blinking Green: Searching for IO-Link devices.
The DI LED indicates digital input on DI (Pin 2).
•
Off: DI signal is low or disconnected
•
Yellow: DI signal is high
The EIP LEDs provide the following information:
•
Green /Blinking = Activity
•
Green/lit LED = Link established
13 Troubleshooting and Technical Support
MD 748i / MD 248i