13.2.2 Md 248I-12-8K/L4-2R2K - Leuze electronic MD 748i Connecting And Operating Instructions

Profinet io-link master
Table of Contents

Advertisement

PWR
MOD
(Module
Status)
NET
(Network
Status)
1-4
Ports 1-4 DI
EIP 1
EIP 2

13.2.2 MD 248i-12-8K/L4-2R2K

The MD 248i-12-8K/L4-2R2K (8-port IP20 DIN rail model) provides these LEDs.
Leuze electronic
MD 748i-11-42/L5-2222 LEDs
A lit green PWR LED indicates that the IO-Link Master is powered.
The MOD LED provides the following information:
Off = No errors or there is no PLC connection
Flashing red
 One or more errors detected when NET is off
 Fatal error when NET is also flashing
Steady red = Maintenance required or demanded
The NET LED provides the following information:
Off = No PLC connection
Steady green = PLC connection established
Flashing red = Fatal error when MOD is also flashing
This LED provides the following information about the IO-Link port.
Off: SIO mode - signal is low or disconnected.
Yellow: SIO mode - signal is high.
Flashing red: Hardware fault - make sure that configured IO-Link settings on the
port do not conflict with the device that is attached:
 Automatic Upload and/or Download is enabled and it is not the same
device.
 Device Validation Mode is enabled and it is not the correct device.
 Data Validation Mode is enabled but there is an error.
Solid red - PDI of the attached IO-Link device is invalid.
Solid Green: An IO-Link device is connected and communicating.
Blinking Green: Searching for IO-Link devices.
The DI LED indicates digital input on DI (Pin 2).
Off: DI signal is low or disconnected
Yellow: DI signal is high
The EIP LEDs provide the following information:
Green /Blinking = Activity
Green/lit LED = Link established
13 Troubleshooting and Technical Support
MD 748i / MD 248i
91

Advertisement

Table of Contents
loading

This manual is also suitable for:

Md 248i

Table of Contents