10.1.2 Downloading Data Storage To The Io-Link Device; 10.1.3 Automatic Device Configuration - Leuze electronic MD 748i Connecting And Operating Instructions

Profinet io-link master
Table of Contents

Advertisement

10.1.2 Downloading Data Storage to the IO-Link Device

There are two methods to download Data Storage using the Configuration | IO-Link Device page:
Automatic Download Enable
Enable option is set to On and one of these conditions exists:
 The original IO-Link device is disconnected and an IO-Link device who's configuration data
differs from the stored configuration data.
 The IO-Link device requests an upload and the Automatic Upload Enable option is set to Off.
Note: Do not enable both Automatic Upload and Download at the same time, the results are not reliable among
IO-Link device manufacturers.
Data Storage Manual Ops: DOWNLOAD
storage from the port to the IO-Link device.
If an IO-Link device with a different Vendor ID and Device ID is attached to the port and a manual
download is attempted, the IO-Link Master issues a hardware fault.

10.1.3 Automatic Device Configuration

Use the following steps to use an IO-Link Master port to configure multiple IO-Link devices with the same
configuration parameters.
1. If necessary, configure the IO-Link device as required for the environment.
2. Click Configuration| IO-Link.
3. Click the EDIT button for the port for which you want to store the data on the IO-Link Master.
4. Click the UPLOAD button.
Figure 44:
5. Click the CONTINUE button to the Continue to upload the data storage on IO-Link Master port
[number] message.
6. Click the Ok button to the
Leuze electronic
- An automatic download occurs when the Automatic Download
Data storage upload
Data storage upload successful on Port [number]
- Selecting the DOWNLOAD button downloads the data
MD 748i / MD 248i
10 Utilizing IO-Link Master Features
message.
69