Configuring the IO-Link Master with STEP 7

3.1

Overview

PROFINET IO configuration procedures vary between software versions but the following configuration
steps are required in all cases. Refer to your STEP 7 documentation, if you require step-by-step
procedures.
1. Download, unzip, and upload the GSD file for the IO-Link Master.
2. Insert the IO-Link Master in the PROFINET IO system.
3. Configure the IP address for the IO-Link Master.
4. Assign the PROFINET Device Name.
5. Set the IO Device Update Time.
6. Configure the IO-Link ports.
a. Configure IO-Link port modules.
b. Configure port status modules.
c. If desired, configure data storage, automatic or manual - upload or download.
d. If desired, configure device validation and data validation.
7. Use chapter 12 PROFINET IO Reference Information to complete configuration after attaching the
IO-Link devices.
The following subsections provides PROFINET IO configuration procedures using
Installing the GSD File (STEP 7 V5.5): see chapter 3.1
Configuring the IO-Link Master (STEP 7 V5.5): see chapter 3.2
Assign IP Address: see chapter 3.3
IP Address Assignment: see chapter 3.4
Device Name Assignment: see chapter 3.5
Setting the IO Device Update Time: see chapter 3.6
3.2

Installing the GSD File (STEP 7 V5.5)

Use the following procedure to install the GSD file for PROFINET IO using STEP 7 V5.5.
1. Unzip GSDML-V2.31-Leuze electronic-IOLink-yyyymmdd.zip to a working directory.
2. Open SIMATIC STEP 7 | HW Config.
3. Use Menu Options | Install GSD Files to install the GSD file.
4. If an older version of the GSD file was installed before, you may need to remove the IO-Link
Master object from an existing project, and reinsert it after the new GSDML file is installed.
3.3

Configuring the IO-Link Master (STEP 7 V5.5)

Select the IO-Link Master from the Hardware Catalog window and insert it into a PROFINET-IO- System
in the HW Config (PROFINET IO -> Additional Field Device -> Gateway -> Leuze electronic IO-Link
Master ->MD 248i-12-8K/L4-2R2K) as shown in Figure 1.
Leuze electronic
3 Configuring the IO-Link Master with STEP 7
MD 748i / MD 248i
STEP 7 V5.5
:
14