3. Click the EDIT button.
4. Enter the PROFINET IO Device Name.
The PROFINET IO Device Name is the same as the name later used to configure PROFINET IO
for the IO-Link Master. The PROFINET IO Device Name is not case-sensitive.
5. If necessary, change the IOL_CALL Function Block Timeout (1-20) value to reflect your
environment.
6. Click SAVE.
Parameter
PROFINET IO Device
Name (Default: empty)
IOL_CALL Function Block
Timeout (1-20)
(Default: 20)
3.6
Setting the IO Device Update Time
Use the following procedure to set the IO Device Update Time.
1. Double-click the Ethernet(1): PROFINET-IO-System (100).
Properties - PROFINET IO-System
2. In the
image below.
Leuze electronic
The device name must be specified according to DNS conventions.
•
Restricted to a total of 240 characters (letters, digits, dash or period)
•
Parts of the name within the device name; in other words, a string
between two periods, must not exceed a maximum of 63 characters.
•
No special characters such as umlauts (ä, ö etc.), brackets,
underscore, slash, blank etc. The dash is the only permitted special
character.
•
The device name must not begin or end with the "-" character.
•
The device name must not begin with numbers.
•
The device name must not have the structure n.n.n.n (n = 0...999).
•
The device name must not begin with the character string "port-xyz-" (x,
y, z = 0...9).
The timeout value in seconds for IOL_CALL function block.
window, select the Update Time tab, as shown in the
MD 748i / MD 248i
3 Configuring the IO-Link Master with STEP 7
Description
24