APG-02
AS-Interface-Handheld
M A N U A L

Advertisement

Table of Contents
loading

Summary of Contents for Leuze electronic APG-02

  • Page 1 APG-02 AS-Interface-Handheld M A N U A L...
  • Page 2 The general terms of delivery for products and services of the electrical industry, as published by the German Elec- trical and Electronic Manufacturers’ Association, shall apply in their latest version, including the supplementary clause: "Extended reservation of title".
  • Page 3: Table Of Contents

    7.2.2 Read and Write ID-code 1 ..................14 7.2.3 Read IO-code......................15 7.2.4 Read and Write Data ....................15 7.2.5 Display and Write Parameters ................. 16 7.2.6 Displaying the Peripheral Fault Flag ............... 16 Error Messages ..................17 Leuze electronic APG-02...
  • Page 4: Declaration Of Conformity

    Declaration of Conformity Declaration of Conformity This manual was written for the following product: • AS-Interface-Handheld APG-02 The AS-Interface-Handheld was designed and manufactured in accordance with applicable European standards and guidelines. A corresponding declaration of conformity can be requested from the manufacturer.
  • Page 5: The Symbols Used

    Failure to heed this warning can lead to personal injury or death and/or damage to equipment. This symbol warns the user of a possible failure. Failure to heed this warning can lead to total failure of the equipment or any other connected equipment. This symbol indicates an important hint. Leuze electronic APG-02...
  • Page 6: Safety

    Electronic waste can be hazardous. Pay attention to local regulations when disposing of the device. The AS-Interface-Handheld APG-02 contains a NiMH battery. In order to ensure environment-friendly disposal, the battery must be disposed of in accordance with the relevant laws for the given country or returned to the distributor.
  • Page 7: As-Interface Version 2.1 Introduction

    Interface slaves on one branch. Moreover, the transmission of analogue values with AS-Inter- face Version 2.1 and higher is as simple as transmitting binary values. For the AS-Interface-Handheld APG-02 described in this manual, only the extension to 62 sub- scribers described below is relevant.
  • Page 8 A and B to maximum 10 ms. The cycle time of conventional slaves remains unchanged, as these are queried in every cycle. If an AS-Interface slave is used which does not support Version 2.1, an address may be assigned only once. APG-02 Leuze electronic...
  • Page 9: Structure Of The As-Interface-Handheld

    Structure of the AS-Interface-Handheld Structure of the AS-Interface-Handheld The battery for the APG-02 is charged on delivery. It is, however, pos- sible that the battery charge is inadequate due to long storage times and self-discharge. This is indicated by a battery symbol on the display.
  • Page 10 - Write the displayed data to the activated slave (not in addressing mode) - Set the operating mode (see chapter 7) Mode - Set the desired address (counting downward) or the desired data - Set the desired address (counting upward) or the desired data APG-02 Leuze electronic...
  • Page 11: Operating Modes

    ADR button. The desired operating mode is set by pressing the MODE button. Press the MODE button until the desired operating mode is displayed in the LCD. The AS-Interface-Handheld APG-02 supports the following operating modes. Display in Operating mode...
  • Page 12: Addressing Mode

    An RD displayed to the left indicates that the activated address is being handled. In addition, the activated address begins to flash in the lower field. The following example should help il- lustrate this behavior: Indicator 2 Indicator 1 Indicator 3 fast flashing APG-02 Leuze electronic...
  • Page 13 If you attempt to describe a conventional slave with an A or B address, error message F6 ap- pears. If you attempt to readdress a Version 2.1 slave to an address without the extension A or B, error message F7 appears. Leuze electronic APG-02...
  • Page 14: Other Operating Modes

    AS-Interface-Handheld with address 0, error mes- sage F5 appears. If automatic address programming is used in the event of a malfunction, the new slave must have the same ID1 and ID2 codes as the slave which is being replaced. APG-02 Leuze electronic...
  • Page 15: Read Io-Code

    Upon pressing the PRG button, the data are transmitted once to the slave and the WR display appears in the display. If the PRG button is held pressed, data are transmitted to the slave until the button is released. Leuze electronic APG-02...
  • Page 16: Display And Write Parameters

    Version 2.1 slaves. This flag can be read with the AS-Interface-Handheld. Activate the slave from which you would like to read this bit. Press the MODE button until PERI appears in the display. The display 0 indicates that no error is present, 1 indicates an error. APG-02 Leuze electronic...
  • Page 17: Error Messages

    Write Data. Pressing the MODE button here activates operating modes which are not sup- ported by the standard slave. Error code F7 always occurs when you attempt to set a Version 2.1 slave to an address when neither the extension A nor B is shown in the display. Leuze electronic APG-02...
  • Page 19 Leuze electronic GmbH + Co. KG Liebigstr. 4 82256 Fuerstenfeldbruck / Germany Telefon +49 8141 5350-0 Telefax +49 8141 5350-190 info@leuze.de www.leuze.com...