Setting Up Local Control
Also refer to the following section Programming the
drive instruction manual (INR-SI47-1225-E) for more information.
Eco
The
panel was intended to be integrated into a building automation
FRENIC-EcoPAK
system and controlled by remote signals. If these signals are not available, the panel can
be set up to be operated locally. Follow these steps to set the panel up for local
operation:
1. Set drive function code F01 to 0.
2. Set drive function code F02 to 2.
3. Set drive function code H96 to 3.
The panel can now be operated directly using the drive keypad.