Fuji Electric FRENIC-EcoPAK Instruction Manual page 13

Non-bypass panels
Table of Contents

Advertisement

BASIC PANEL STARTUP
CAUTION
Make sure all power and control wiring is completed before proceeding.
As with all electrical equipment installations, insure all safety/wiring instructions have
been followed in accordance with this product's manuals and local and national
codes.
1. Energize panel by turning disconnect switch to the 'ON' position.
2. Set drive parameters for the connected motor (refer to table below). Set drive speed
control to 'Local' by pushing the 'REM/LOC' button on the drive keypad.
3. Push the 'FWD' button on the keypad to energize the drive. Use the Up/Down keys
to change the drive speed as necessary.
4. Check that the motor rotates in the correct direction. To change, refer to the
Troubleshooting section in this manual.
5. Measure and record motor FLA if required. Allow motor to run at full speed for a
sufficient time to insure panel-mounted overloads are properly set. Adjust, if
necessary.
6. Push the 'Stop' button on the keypad and allow the motor to come to a complete
stop.
7. De-energize panel.
8. Record startup data and change any parameters as necessary.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Page 13 of 22

Advertisement

Table of Contents
loading

Table of Contents