Parameterizing
7.2 Parameterizing via the user interface
Voltage input
Selection
Connection type
Use PTs?
Measuring voltage
PT PRIMARY
(provided Use PTs?
PT SECONDARY
(provided Use PTs?
92
Range
3P4W
3 phases, 4 conductors, unbalanced load
3P3W
3 phases, 3 conductors, unbalanced load
3P4WB
3 phases, 4 conductors, balanced load
3P3WB
3 phases, 3 conductors, unbalanced load
1P2W
1 phase, 2 conductors, unbalanced load
ON: Measurement using voltage transformers.
When measuring via voltage transformer, the device must know the
voltage transformation ratio. For this purpose, the primary and sec-
ondary voltages must be specified in the fields "PT PRIMARY" and
"PT SECONDARY".
When changing from direct measurement to measurement using volt-
age transformers, the device accepts the last set reference measuring
voltage as the secondary voltage and as the primary voltage.
OFF: Measurement directly on the low-voltage system.
When changing from measurement using voltage transformers to di-
rect measurement, the device accepts the last set secondary voltage
as the reference measuring voltage.
1 V ... 690 V, freely adjustable (max. 600 V for UL)
1 V ... 500 V, freely adjustable (PAC4200 with extra-low voltage sup-
ply unit)
1 V ... 999999 V, freely adjustable
ON)
1 V ... 690 V, freely adjustable (max. 600 V for UL)
ON)
1 V ... 500 V, freely adjustable (PAC4200 with extra-low voltage sup-
ply unit)
Factory setting
3P4W
400 V
System Manual, 05/2019, A5E02316180B-05
OFF
400 V
289 V
400 V
289 V
PAC4200