Parameterizing
7.2 Parameterizing via the user interface
Selection
MODE
(only with PULSE INPUT)
PULSES PER UNIT
(only with PULSE INPUT)
UNIT
(only with PULSE INPUT)
TEXT
TEXT
(only with PULSE INPUT →
TEXT)
TARGET
RELATED COUNTER
Target
PROCESS&PULSE
PULSE COUNTER
PULSE COUNTER 1 ... n
PROCESS COUNTER
PROCESS COUNTER
kWh/kVAR/kVAh
100
Range
Counting of pulses or edges.
PULSE: Pulses are counted.
EDGE: Edges are counted.
Number of pulses that must be received per unit in order for the counter
to be incremented by "1".
1 ... 999
The reference unit is defined in the "UNIT" field.
Unit to be counted when counting the pulses or edges received:
kWh (active energy)
kvarh (reactive energy)
"TEXT" stands for a user-definable unit, e.g. m
The text sequence used to name the unit must be defined via the com-
munication interface.
The defined text sequence is displayed in the "TEXT" field when you
select "TEXT".
Text sequence used to name the unit to be counted.
See "UNIT" field.
You will find more detailed information in the following table.
The associated user-defined pulse counter is displayed here inde-
pendently of the action selected.
This function is only available if at least one SENTRON PAC 4DI/2DO
expansion module is plugged into the SENTRON PAC.
Description
Relates to:
All process energy counters
The process operating hours counter
All pulse counters
All pulse counters
Specific pulse counter
All process energy counters
Specific process energy counter
/h or pieces.
3
START/
COPY/
STOP
RESET
-
-
-
-
-
-
x
x
-
x
System Manual, 05/2019, A5E02316180B-05
Factory setting
PULSE
1
-
-
-
-
-
RESET
x
x
x
x
x
PAC4200