Minimum Values With A Time Stamp And The Function Codes 0X03 And 0X04 - Siemens SENTRON PAC4200 Manual

Power monitoring device
Hide thumbs Also See for SENTRON PAC4200:
Table of Contents

Advertisement

A.2.9

Minimum values with a time stamp and the function codes 0x03 and 0x04

Addressing the minimum values with a time stamp
Table A- 18
Available measured variables: Minimum values with time stamp
Offset
Number of
Name
registers
6001
6
Minimum Voltage L1-N with Time
6007
6
Minimum Voltage L2-N with Time
6013
6
Minimum Voltage L3-N with Time
6019
6
Minimum Voltage L1-L2 with Time
6025
6
Minimum Voltage L2-L3 with Time
6031
6
Minimum Voltage L3-L1 with Time
6037
6
Minimum Current L1 with Time
6043
6
Minimum Current L2 with Time
6049
6
Minimum Current L3 with Time
6055
6
Minimum Apparent Power L1 with Time
6061
6
Minimum Apparent Power L2 with Time
6067
6
Minimum Apparent Power L3 with Time
6073
6
Minimum Active Power L1 with Time
6079
6
Minimum Active Power L2 with Time
6085
6
Minimum Active Power L3 with Time
6091
6
Minimum Reactive Power L1 (Qn) with Time Float + time stamp
6097
6
Minimum Reactive Power L2 (Qn) with Time Float + time stamp
6103
6
Minimum Reactive Power L3 (Qn) with Time Float + time stamp
6109
6
Minimum Total Reactive Power L1 (Qtot)
with Time
6115
6
Minimum Total Reactive Power L2 (Qtot)
with Time
6121
6
Minimum Total Reactive Power L3 (Qtot)
with Time
6127
6
Minimum Reactive Power L1 (Q1) with Time Float + time stamp
6133
6
Minimum Reactive Power L2 (Q1) with Time Float + time stamp
6139
6
Minimum Reactive Power L3 (Q1) with Time Float + time stamp
6145
6
Minimum Power Factor L1 with Time
6151
6
Minimum Power Factor L2 with Time
6157
6
Minimum Power Factor L3 with Time
6163
6
Minimum cos φ L1 with Time
6169
6
Minimum cos φ L2 with Time
6175
6
Minimum cos φ L3 with Time
6181
6
Minimum Displacement Angle L1 with Time
6187
6
Minimum Displacement Angle L2 with Time
6193
6
Minimum Displacement Angle L3 with Time
PAC4200
System Manual, 05/2019, A5E02316180B-05
Format
Unit
Float + time stamp
V
Float + time stamp
V
Float + time stamp
V
Float + time stamp
V
Float + time stamp
V
Float + time stamp
V
Float + time stamp
A
Float + time stamp
A
Float + time stamp
A
Float + time stamp
VA
Float + time stamp
VA
Float + time stamp
VA
Float + time stamp
W
Float + time stamp
W
Float + time stamp
W
VAR
VAR
VAR
Float + time stamp
VAR
Float + time stamp
VAR
Float + time stamp
VAR
VAR
VAR
VAR
Float + time stamp
-
Float + time stamp
-
Float + time stamp
-
Float + time stamp
cos φ
Float + time stamp
cos φ
Float + time stamp
cos φ
Float + time stamp
°
Float + time stamp
°
Float + time stamp
°
Appendix
A.2 Modbus
Value
Access
range
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
0 ... 1
R
0 ... 1
R
0 ... 1
R
-
R
L1
-
R
L2
-
R
L3
-
R
-
R
-
R
165