Siemens SENTRON PAC4200 Manual page 13

Power monitoring device
Hide thumbs Also See for SENTRON PAC4200:
Table of Contents

Advertisement

Description
2.1 Performance features
● Detection of voltage dips, overvoltage and voltage interruptions with user-defined
threshold values
● Measurement of N (neutral) conductor current
● Measurement of residual current and PE conductor current through external summation
current transformer
● Measurement of physical variables (e.g. temperature, pressure, humidity) with external
0/4 mA to 20 mA transmitter
Using optionally available expansion module "I(N), I(DIFF), Analog" (MLFB: 7KM9200-
1)
0AD00-0AA0)
Manual 7KM PAC expansion module I(N), I(Diff), analog
(https://support.industry.siemens.com/cs/ww/en/view/109746834)
Counters and power demand
● A total of 10 energy counters capture reactive energy, apparent energy, and active
energy for off-peak and on-peak, import and export.
● Energy consumption for active energy, reactive energy and apparent energy per day and
tariff for 366 days.
● Two configurable universal counters for counting:
– Limit violations
– Status changes at the digital input
– Status changes at the digital output
– Pulses of a connected pulse encoder (e.g. from electricity, gas, or water meters). The
● Operating hours counter for monitoring the operating time of a connected load. Counts
only in the case of energy counting above an adjustable threshold.
● One apparent energy counter, one active energy counter, and one reactive energy
counter for detecting the total energy import, regardless of the active tariff for display on
the device.
● One apparent energy counter, one active energy counter, and one reactive energy
counter for detecting the power consumption of a manufacturing process. The process
energy counters can be started and stopped by means of the available digital inputs.
● Operating hours counter for recording the duration of a manufacturing process. The start
and stop commands of the digital input that controls the process energy counter start and
stop the operating hours counter. Up to 10 counters for detecting the consumption of any
media via digital inputs if the optionally available SENTRON PAC 4DI/2DO expansion
modules are used. Consumption (e.g. of gas, water, compressed air, electrical current)
can thus be recorded using simple media counters with a pulse output.
The display texts can be freely parameterized in a user-friendly way using the
SENTRON powerconfig configuration software.
12
1)
pulse shape and time response must correspond to the signal shape described in the
IEC 62053-31 standard.
1)
1)
System Manual, 05/2019, A5E02316180B-05